INSTALLATION INSTRUCTIONS - Lennox
INSTALLATION INSTRUCTIONS - Lennox
INSTALLATION INSTRUCTIONS - Lennox
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
INTEGRATED CONTROL BOARD<br />
(Automatic Hot Surface Ignition System)<br />
HUM<br />
LINE<br />
XFMR<br />
EAC<br />
COOL<br />
HEAT<br />
PARK<br />
FLAME<br />
NEUTRALS<br />
TERMINAL DESIGNATIONS<br />
Humidifier (120VAC)<br />
Input (120VAC)<br />
Transformer (120VAC)<br />
Electronic Air Cleaner (120VAC)<br />
Blower − Cooling Speed (120VAC)<br />
Blower − Heating Speed (120VAC)<br />
Dead terminals to park alternate spd taps<br />
Flame senser<br />
Neutral terminals (120VAC)<br />
3 AMP, 32 VAC FUSE<br />
BLOWER OFF<br />
DELAY JUMPER<br />
FIGURE 42<br />
Unit Start−Up<br />
FOR YOUR SAFETY READ BEFORE OPERATING<br />
WARNING<br />
Do not use this furnace if any part has been underwater.<br />
A flood−damaged furnace is extremely dangerous.<br />
Attempts to use the furnace can result in<br />
fire or explosion. Immediately call a qualified service<br />
technician to inspect the furnace and to replace<br />
all gas controls, control system parts, and electrical<br />
parts that have been wet or to replace the furnace,<br />
if deemed necessary.<br />
WARNING<br />
Danger of explosion. Can cause injury<br />
or product or property damage. Should<br />
the gas supply fail to shut off or if<br />
overheating occurs, shut off the gas<br />
valve to the furnace before shutting off<br />
the electrical supply.<br />
CAUTION<br />
Before attempting to perform any service or maintenance,<br />
turn the electrical power to unit OFF at disconnect<br />
switch.<br />
Priming Condensate Trap<br />
The condensate trap should be primed with water prior to<br />
start−up to ensure proper condensate drainage. Either<br />
pour 10 fl. oz. (300 ml) of water into the trap, or follow<br />
these steps to prime the trap:<br />
1 − Follow the lighting instructions to place the unit into operation.<br />
2 − Set the thermostat to initiate a heating demand.<br />
3 − Allow the burners to fire for approximately 3 minutes.<br />
4 − Adjust the thermostat to deactivate the heating demand.<br />
5 − Wait for the combustion air inducer to stop. Set the<br />
thermostat to initiate a heating demand and again allow<br />
the burners to fire for approximately 3 minutes.<br />
Page 31