Dimensioning tables<br />

7.3.3 Kalzip ProDach (adjacent) with aluminium clips<br />

Clip fixing: directly to ProDach fixing rail.<br />

(fasteners: SFS SDK2-S-377-6.0 x L). 2 fasteners per clip.<br />

Line<br />

Kalzip<br />

type<br />

Sheet thickness<br />

t in mm<br />

Pressing loads*<br />

kN/m 2<br />

Uplifting loads<br />

kN/m 2<br />

0.48 0.90 1.44 1.60 1.98 2.56 3.52<br />

2.40 2.20 1.60 1.40 1.10 0.80 0.50<br />

1 AF 65/333 0.80 Pressing loads are<br />

2<br />

3<br />

4<br />

0.90<br />

1.00<br />

1.20<br />

transmitted directly<br />

through contact onto<br />

the substructure<br />

2.40<br />

2.90<br />

2.90<br />

2.60<br />

2.80<br />

2.90<br />

1.80<br />

2.00<br />

2.20<br />

1.60<br />

1.80<br />

2.00<br />

1.30<br />

1.60<br />

1.80<br />

0.90<br />

1.20<br />

1.40<br />

0.70<br />

0.90<br />

1.10<br />

5<br />

6 AF 65/434 0.80 Pressing loads are 2.30 2.00 1.20 1.00 0.80 0.50 0.30<br />

7 AS 65/422 0.90 transmitted directly 2.70 2.30 1.40 1.20 0.90 0.70 0.50<br />

8 1.00 through contact onto 2.90 2.50 1.80 1.40 1.20 0.90 0.60<br />

9 1.20 the substructure 3.00 2.70 2.00 1.80 1.50 1.10 0.70<br />

Separate design calculations are required for the substructure. Please contact: DEUTSCHE ROCKWOOL MINERALWOLL GMBH & CO. OHG.<br />

Rockwool Straße 37-41. D-45966 Gladbeck. T +49 (0)2043/408-0. F +49 (0)2043/408-444.<br />

The table does not apply to Kalzip DuoPlus.<br />

Supporting width in [m]<br />

7.3.4 Kalzip AluPlusSolar*<br />

When using Kalzip aluminium clips. Details on Kalzip composite clips available on request.<br />

Clip fixing: directly onto steel trapezoidal substructure t min<br />

= 0.75 mm.<br />

2 fasteners per clip (SFS SDK2-S-377-6.0 x L).<br />

Line Kalzip<br />

type<br />

Sheet thickness<br />

t in mm<br />

Pressing loads*<br />

kN/m 2<br />

Uplifting loads<br />

kN/m 2<br />

0.75 1.00 1.25 0.90 1.44 1.60 1.93 2.56 3.52<br />

1 AF 65/537 1.00 2.00 1.90 1.80 1.20 0.90 0.70 0.60 0.50 0.40<br />

*in accordance with DIN 1052<br />

*The supporting widths for snow load also apply to the wind suction load in the normal range for building heights 100 m.<br />

If the Kalzip profiled sheets are not fitted with rigid thermal insulation. access is only possible using load spreading equipment. The values stated are guide<br />

values. They do not serve as a replacement for project-specific consultations. Separate design calculations are required for the substructure. The values<br />

50 Kalzip