Fill the<br />

thermostat<br />

3. Commissioning<br />

3.4 Filling Thermofluid<br />

Unichiller (Chiller)<br />

UC007 1-3<br />

Please note:<br />

The thermostat is fitted out with an overfill<br />

protection. When the fluid level exceeds<br />

the max mark in the sight-glass, the fluid<br />

begins to outflow from the overflow connection<br />

(8). An overflow of the internal<br />

tank (wich could flood the machine internals)<br />

can thus be avoided.<br />

Warning:<br />

The overflow connection should never be<br />

closed, the fluid should be able to flow out<br />

without hindrance. However it is recommended<br />

with frequent change of the liquid<br />

or the application and/or with the first<br />

commissioning to put a hose on the overflow<br />

connection and to place the other end<br />

into a suitable receiver.<br />

Make a hose connection to your external<br />

application and make sure that everything is<br />

leakproof.<br />

Take off the lid of the filler connection (5) and<br />

slowly fill the thermal fluid.<br />

The fluid level should allways be between<br />

MIN and MAX on the level indicator.<br />

Switch the unit on with the main switch (2).<br />

The thermostat starts circulation and the fluid<br />

is pumped into your application. If there is<br />

no fluid in the application yet, the level in the<br />

Unichiller will lower continualy, please refill<br />

with fluid untill the level stays constant.<br />