5.4 Calculation of the request in air/water units<br />

5.4.1 Used inlets<br />

• Water temperature analogue inlet, evaporator-condenser inlet<br />

• Digital inlet of summer/winter commutation.<br />

5.4.2 Used parameters<br />

• Summer regulation setpoint<br />

• Winter regulation setpoint<br />

• Temperature regulation band<br />

• Unit selection air/water type<br />

5.4.3 Used outlets<br />

• All the outlets reserved at the compressors<br />

5.5 Working description<br />

The calculation of the thermostatic request of the unit is based on a control of proportional type<br />

with lateral band, based on the temperature measure of the inlet water to the evaporator/<br />

condenser coil. If the unit is in chiller mode or heat pump the regulation band will be fixed at the<br />

right or left of the setpoint respectively.<br />

5.5.1 Temperature regulation in chiller mode<br />

Regulation example of the temperature in single-compressor units<br />

PWR<br />

STEP1<br />

STPM<br />

EIWT[°C]<br />

BND<br />

PWR Integrated power<br />

STEP1 Power step 1<br />

STPM Main regulation setpoint<br />

BND Regulation band<br />

EIWT[°C] Evaporator inlet water temperature<br />

There are 2 possible ways of compressor management: grouped and equalised. For default is<br />

equalised.<br />

The selection is done by the “En.layer device” parameter in the “configuration menu”.<br />

Example<br />

of grouped regulation (En.layer device=N) in twin-circuit four-compressor units:<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 18