The delay time at the activation of the pre-ventilation compressors is a settable parameter<br />

protected from specific user’s password.<br />

7.2.3 Post-ventilation<br />

The post-ventilation function it’s possible activate it only in chiller working (parameter protected<br />

from manufacturer’s password), according to, after a high pressure alarm (by pressure switch or<br />

trasductor), the fan of the related circuit will be activated at maximum capacity for a time settable<br />

from maintenance parameter , protected from specific password.<br />

7.2.4 Heat pump working<br />

RBC<br />

MAXV<br />

CFPWM<br />

MINV<br />

HCOFF<br />

CFONOFF<br />

STPC<br />

CPRS[bar]<br />

CPRS Condensation pressure<br />

STPC Condensation setpoint<br />

RBC Condensation regulation band<br />

HCOFF Cut-off steps hysteresis<br />

MINV Condensation fans minimum speed<br />

MAXV Condensation fans maximum speed<br />

CFONOFF Condensation fan control from On-Off digital outlet<br />

CFPWM Condensation fan control from PWM analogue outlet<br />

The activation of a defrost cycle will cause the switch-off of the related fan group in heat pump<br />

mode.<br />

7.2.5 High temperature/pressure pre-alarm<br />

RBC<br />

HYST_P<br />

HYSTA_HP<br />

CPRS[bar] / TC[°C]<br />

STPC<br />

THR_P<br />

THRA_H<br />

STPC Condensation regulation setpoint<br />

RBC Condensation regulation band<br />

THR_P High condensation prevention threshold<br />

HYST_P High condensation prevention hysteresis<br />

THRA_HP High condensation alarm threshold<br />

HYSTA_HP High condensation alarm hysteresis<br />

CPRS / TC Condensation Pressure/Temperature<br />

It’s possible activate a prevention function of high pressure/temperature of condensation,<br />

according to, after a threshold and an hysteresis are set-up, a fan activation step is checked, that<br />

will bring them at the maximum speed, with the purpose to prevent the intervention of the high<br />

condensation alarm, with following compressor’s switch-off.<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 26