8.5 Condensing fan<br />

During a defrost cycle the condensation fan/s will be switched-off.<br />

It will be activated during the dripping process, if the process from manufacturer’s opportune<br />

parameter protected from specific password is activated. The switch-off period of a compressor<br />

after a defrost, is known as dripping process.<br />

8.6 Low pressure alarm from pressure<br />

In the whole defrost process, the circuit’s low-pressure alarm<br />

be ignored.<br />

switch<br />

Only at the end of the dripping process (DE point of the previous graphic) the<br />

according to the set-up by-pass times will be activated.<br />

from pressure switch (digital inlet) will<br />

control of the alarm<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 32