Code Alarm Compressor Fans OFF<br />

Pump Unit OFF Re-set Delay Notes<br />

description s OFF<br />

OFF<br />

protector<br />

then, circ.2 fans off,<br />

interventions)<br />

With switched-off compressor the state of the alarm is ignored(Kriwan)<br />

only if both circ.2<br />

compressors in off<br />

020 Condensation Yes Yes 1 and 2 circuit No No Automatic – <strong>Manual</strong> 0 s<br />

fan thermal<br />

(bound by the<br />

protection<br />

number of set-up<br />

interventions)<br />

002 Evaporator Yes Yes Only ON Automatic – <strong>Manual</strong> Settable at t he start<br />

antifreeze<br />

pump (bound by<br />

the of the unit<br />

alarm<br />

number of set-up<br />

interventions)<br />

030 Faulted probe Yes Yes Yes Yes Automatic 60 s<br />

B1<br />

031 Faulted probe Circ.1<br />

Only if connected Only if Only if Automatic<br />

60 s<br />

B2<br />

compressor/s<br />

with 1 circuit connect connecte<br />

ed with d with 1<br />

1 circuit circuit<br />

032 Faulted probe Circ.1<br />

Only if connected Only if Only if Automatic<br />

60 s<br />

B3<br />

compressor/s<br />

with 1 circuit connect connecte<br />

ed with d with 1<br />

1 circuit circuit<br />

033 Faulted probe Circ. 1 Only if connected Only if Only if Automatic 60 s<br />

B4<br />

compressor/s<br />

with 1 circuit connect connecte<br />

ed with d with 1<br />

1 circuit<br />

circuit<br />

034 Faulted probe Circ.2 If the fans are No No Automatic<br />

60 s<br />

B5<br />

compressor/s<br />

connected to the<br />

compres.<br />

state,<br />

then, circ.2 fan off<br />

035 Faulted probe Circ. 1 Only if connected Only if Only if Automatic<br />

60 s<br />

B6<br />

compressor/s with 1 circuit, connect connecte<br />

otherwise if the fans ed with<br />

d with 1<br />

are connected at the 1 circuit circuit<br />

comp ressor state,<br />

then, circ.1 fan off<br />

036 Faulted probe Circ. 2 If t he fans are No No Automatic 60 s<br />

B7<br />

compressor/s connected to the<br />

comp ressors state,<br />

then, circ.2 fan off<br />

037 Faulted probe Circ. 2 If t he fans are No No Automatic 60 s<br />

B8<br />

compressor/s connected to the<br />

compressors state,<br />

then, circ.2 fan off<br />

038 B9 faulted Circ.2 If the fans are No No Automatic 60 s<br />

probe<br />

compressor/s connected to the<br />

compressors state,<br />

then, circ.2 fan off<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 38