6 COMPRESSORS<br />

6.1 Refrigerating circuit types<br />

The software can manage the following types of unit, all with the chance of working in chiller mode<br />

or heat pump:<br />

single-circuit – single-compressor<br />

single-circuit – twin-compressor<br />

twin-circuit – twin-compressor<br />

twin-circuit – four-compressor<br />

Tandem compressors configuration<br />

Tandem compressors configuration<br />

The compressors will be of hermetic type, without any chance of power modulation by choking<br />

steps.<br />

6.2 Safety delay times<br />

For each compressor will be managed some safety delay times with the purpose to protect the<br />

working of the device restricting the working to particular conditions given from the manufacturer of<br />

the same compressor.<br />

The managed times will be:<br />

1. switch-off minimum time<br />

2. minimum time among following switch-on of the same compressor<br />

3. minimum time of working<br />

4. time among switch-on of different compressors<br />

5. time among switch-off of different compressors<br />

6.2.1 Switch-off minimum time<br />

Between a switch-off and a switch-on of the same compressor a safety time must be respected.<br />

That time will be applied even at the return from blackout deactivating the thermostatic control,<br />

protecting the compressor from switch-off of not exact last.<br />

6.2.2 Time between starting times of the same compressor<br />

From a switch-on to the next must be respected a safety time with the purpose of guarantee the<br />

minimum number of starting times per hour of the compressor.<br />

Working minimum time<br />

After the switch-on a compressor must work for a minimum time same at the indicated time<br />

independently from the thermostatic request.<br />

The switch-off can be immediate after an alarm, delayed for a decrease of request with active time.<br />

6.2.3 Time among switch-on of different compressors / Time among<br />

switch-off off different compressors<br />

In twin/four-compressor units are applied two different safety times between the switch-on and<br />

switch-off of following compressors.<br />

The applied time among the switches-on avoids the electric circuit overloud caused by the<br />

possible contemporary switch-on of two devices (for example after an alarm).<br />

The applied time among the switches-off makes gradual the power decrease in the circuit,<br />

avoiding then swinging of the requests between switch-on and switch-off.<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />