6 COMPRESSORS<br />
6.1 Refrigerating circuit types<br />
The software can manage the following types of unit, all with the chance of working in chiller mode<br />
or heat pump:<br />
single-circuit – single-compressor<br />
single-circuit – twin-compressor<br />
twin-circuit – twin-compressor<br />
twin-circuit – four-compressor<br />
Tandem compressors configuration<br />
Tandem compressors configuration<br />
The compressors will be of hermetic type, without any chance of power modulation by choking<br />
steps.<br />
6.2 Safety delay times<br />
For each compressor will be managed some safety delay times with the purpose to protect the<br />
working of the device restricting the working to particular conditions given from the manufacturer of<br />
the same compressor.<br />
The managed times will be:<br />
1. switch-off minimum time<br />
2. minimum time among following switch-on of the same compressor<br />
3. minimum time of working<br />
4. time among switch-on of different compressors<br />
5. time among switch-off of different compressors<br />
6.2.1 Switch-off minimum time<br />
Between a switch-off and a switch-on of the same compressor a safety time must be respected.<br />
That time will be applied even at the return from blackout deactivating the thermostatic control,<br />
protecting the compressor from switch-off of not exact last.<br />
6.2.2 Time between starting times of the same compressor<br />
From a switch-on to the next must be respected a safety time with the purpose of guarantee the<br />
minimum number of starting times per hour of the compressor.<br />
Working minimum time<br />
After the switch-on a compressor must work for a minimum time same at the indicated time<br />
independently from the thermostatic request.<br />
The switch-off can be immediate after an alarm, delayed for a decrease of request with active time.<br />
6.2.3 Time among switch-on of different compressors / Time among<br />
switch-off off different compressors<br />
In twin/four-compressor units are applied two different safety times between the switch-on and<br />
switch-off of following compressors.<br />
The applied time among the switches-on avoids the electric circuit overloud caused by the<br />
possible contemporary switch-on of two devices (for example after an alarm).<br />
The applied time among the switches-off makes gradual the power decrease in the circuit,<br />
avoiding then swinging of the requests between switch-on and switch-off.<br />