8 DEFROST<br />

8.1.1 Used inlets<br />

• Condenser temperature analogic inlet<br />

• Condensation pressure analogic inlet<br />

8.1.2 Used parameters<br />

• Defrost type<br />

• Defrost starting temperature threshold<br />

• Defrost ending temperature threshold<br />

• Defrost starting pressure threshold<br />

• Defrost ending pressure threshold<br />

• Delay among following defrosts<br />

• Defrost activation delay<br />

• Defrost maximum last<br />

• Delay between compressor and valve at the defrost start<br />

• Delay between compressor and valve at the end of the defrost<br />

• Fan forcing activation in dripping phase<br />

• Fan speed set-up in dripping phase<br />

8.1.3 Used outlets<br />

• Digital outlet of the refrigerating cycle inversion<br />

• All the digital outlets related to the compressors<br />

• All the digital/analogue outlets related to the condensation fans<br />

8.2 Working description<br />

C PT [bar/ ºC]<br />

DefrOffTHR<br />

DefrOnTHR<br />

t [s]<br />

∆t1 ∆t2 ∆t3 DefrAct<br />

DefrOffTHR<br />

DefrOnTHR<br />

CPT<br />

∆t 1…3<br />

DefrAct<br />

T<br />

Defrost end threshold<br />

Defrost start threshold<br />

Condensation pressure/temperature<br />

Pressure/temperature permanence partial time in the defrost<br />

activation zone<br />

Active defrost<br />

Time<br />

Only in heat pump mode we can have the defrost activation.<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 28