8 DEFROST<br />
8.1.1 Used inlets<br />
• Condenser temperature analogic inlet<br />
• Condensation pressure analogic inlet<br />
8.1.2 Used parameters<br />
• Defrost type<br />
• Defrost starting temperature threshold<br />
• Defrost ending temperature threshold<br />
• Defrost starting pressure threshold<br />
• Defrost ending pressure threshold<br />
• Delay among following defrosts<br />
• Defrost activation delay<br />
• Defrost maximum last<br />
• Delay between compressor and valve at the defrost start<br />
• Delay between compressor and valve at the end of the defrost<br />
• Fan forcing activation in dripping phase<br />
• Fan speed set-up in dripping phase<br />
8.1.3 Used outlets<br />
• Digital outlet of the refrigerating cycle inversion<br />
• All the digital outlets related to the compressors<br />
• All the digital/analogue outlets related to the condensation fans<br />
8.2 Working description<br />
C PT [bar/ ºC]<br />
DefrOffTHR<br />
DefrOnTHR<br />
t [s]<br />
∆t1 ∆t2 ∆t3 DefrAct<br />
DefrOffTHR<br />
DefrOnTHR<br />
CPT<br />
∆t 1…3<br />
DefrAct<br />
T<br />
Defrost end threshold<br />
Defrost start threshold<br />
Condensation pressure/temperature<br />
Pressure/temperature permanence partial time in the defrost<br />
activation zone<br />
Active defrost<br />
Time<br />
Only in heat pump mode we can have the defrost activation.<br />