than the set delta, if the control by opportune manufacturer’s parameter protected from specific<br />
password is activated, after the set delay, the alarm will be signalled.<br />
11.7 Phases control management<br />
11.7.1 Used inlets<br />
• Three-phase card for phase sequence control and voltage measure<br />
11.7.2 Used parameters<br />
• Feed nominal voltage<br />
• Type of feed<br />
• Phase monitor alarm activation (both tension min/max alarms and wrong phase sequence)<br />
• Network frequency<br />
• Minimum voltage treshold<br />
• Maximum voltage threshold<br />
11.7.3 Used outlets<br />
• Relay digital outlet of cumulative alarm<br />
11.7.4 Working description<br />
The pCO1OEM onboard card installation of a phase monitor card and phase wideness measure is<br />
provided, according to that the direct verify of the right link of the unit and the probable anomaly<br />
absorption of the phases is possible.<br />
The pCO OEM controller will be able to monitor the exact phases system in the three-phase systems,<br />
and if this is not correct, it will signal it by a manual reset alarm with following switch-off of all the linked<br />
loads.<br />
That alarm can be disabled by a special parameter protected from specific password, visible/adjustable<br />
from PGD interface.<br />
Ass well as the correct sequence control of the phases it provides at the control of the wideness<br />
according to two set minimum and maximum thresholds.<br />
According to the type of used feed system, the program will be able to decide if it’s whether or not the<br />
case to feed the measured F-N o F-F voltage (neutral-phase or phase-phase), the following table reports<br />
the provided correspondences:<br />
Type of Voltage Type of voltage<br />
distribution<br />
measurement<br />
1 F + N 230 V F-N<br />
3 F + N 400 V F-F<br />
3 F 230 V F-F<br />
From the table results that in three-phase systems the indications of phase-phase voltage will be always<br />
supplied.<br />
To indicate the type of used distributions, a set-up parameter that indicates the provided phases number<br />
and if it’s whether or not present the neutral will be introduced; that parameter will be protected from<br />
specific manufacturer’s password and visible/adjustable by PGD user’s interface.<br />
From the installed unit values is possible to determine the working voltage threshold over those the unit<br />
working is not guaranteed; will be then introduced a set-up parameter of the system’s nominal voltage.<br />
That value protected from manufacturer’s password is visible by PGD user’s interface will allow the<br />
preventive definition of the thresholds of minimum and maximum working voltage.<br />
Normally the tolerance is + 10%, on the basis of that values, as soon as the voltage value of nominal<br />
feed is set-up, the program will do a rapid calculation, automatically setting the thresholds of the width’s<br />
maximum and minimum alarm of the phases.<br />
If adjust those values for particular unit requirements is necessary, will be possible enter at the<br />
opportune parameters, protected from manufacturer’s password.<br />
<strong>Rhoss</strong> S.p.A. S.A.T.<br />
Rev. 1.0 20/01/05 42