Defrost temperature circ-1 B3 pGE B3 conf. NTC (like for single circuit)<br />

Recovery temperature 1 / Outside air B4 pGE B4 conf. NTC (like for single circuit)<br />

temperature<br />

Recovery temperature 2 B5 pGE B5 conf. NTC (like for single circuit)<br />

Condenser pressure circ-1 B6 pGE B6 conf. 0-5V (like for single circuit)<br />

Water outlet temperature circ-2 B7 pGE B7 conf. NTC<br />

Defrost temperature circ-2 B8 pGE B8 conf. NTC<br />

Condenser pressure circ-2 B9 PCOE address 0 B1 conf. 0-5V<br />

2.5 Considerations<br />

The way of working decided for the digital inlets (except the remote On/Off inlet) provides the high<br />

logic state (1) in case of opened contact, like already did for all the applications on any Carel<br />

hardware.<br />

At the qualification of the pressure transducer the software will automatically proceed at the<br />

following operations:<br />

• disqualification of the analogue inlet, related to the condensing coil temperature<br />

• control of the defrost process according to the pressure values of condensation instead of the<br />

temperature of the condensing coil.<br />

The disconnection of the pressure trasductor will involve the automatic return at working in<br />

temperature of all the interested functions and if qualified, at the exclusion of the proportional<br />

control of condensation.<br />

2.6 Digital inlets/outlets Configuration<br />

To allow the interface dialogue of the system with different nature devices, among the<br />

manufacturer parameters, protected by specific passwords, are provided with set up parameters of<br />

the working modality of the inlets and the digital outlets.<br />

They can be clearly set up, the working logic of each inlet or outlet, on the main card according to<br />

the following correspondences:<br />

Digital inlets<br />

N.C. during the normal working of the unit the contact is closed (logic state 0), the contact<br />

opening, involves an action from the program (logic state 1)<br />

N.O. during the normal working of the unit the contact is opened (logic state 0), the contact<br />

closing, involves an action from the program (logic state 1)<br />

Digital outlets<br />

N.C. the activation of a loading connected to the card pCO1OEM is caused from a closing of an<br />

associated contact (references to the inlet/outlet tables)<br />

N.O. the activation of a loading connected to the card pCO1OEM is caused from an opening of an<br />

associated contact (references to the inlet/outlet tables)<br />

2.7 B4 multifunction analogue inlet<br />

The management of the B4 analogue inlet provides distinct modalities if is qualified or no, the heat<br />

recovery function and the compensation of the adjusting setpoint based on the values of the<br />

outside temperature.<br />

The following table summarises the correspondences between the analogue inlet functionality and<br />

particular unit enabled functions.<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 8