Defrost temperature circ-1 B3 pGE B3 conf. NTC (like for single circuit)<br />
Recovery temperature 1 / Outside air B4 pGE B4 conf. NTC (like for single circuit)<br />
temperature<br />
Recovery temperature 2 B5 pGE B5 conf. NTC (like for single circuit)<br />
Condenser pressure circ-1 B6 pGE B6 conf. 0-5V (like for single circuit)<br />
Water outlet temperature circ-2 B7 pGE B7 conf. NTC<br />
Defrost temperature circ-2 B8 pGE B8 conf. NTC<br />
Condenser pressure circ-2 B9 PCOE address 0 B1 conf. 0-5V<br />
2.5 Considerations<br />
The way of working decided for the digital inlets (except the remote On/Off inlet) provides the high<br />
logic state (1) in case of opened contact, like already did for all the applications on any Carel<br />
hardware.<br />
At the qualification of the pressure transducer the software will automatically proceed at the<br />
following operations:<br />
• disqualification of the analogue inlet, related to the condensing coil temperature<br />
• control of the defrost process according to the pressure values of condensation instead of the<br />
temperature of the condensing coil.<br />
The disconnection of the pressure trasductor will involve the automatic return at working in<br />
temperature of all the interested functions and if qualified, at the exclusion of the proportional<br />
control of condensation.<br />
2.6 Digital inlets/outlets Configuration<br />
To allow the interface dialogue of the system with different nature devices, among the<br />
manufacturer parameters, protected by specific passwords, are provided with set up parameters of<br />
the working modality of the inlets and the digital outlets.<br />
They can be clearly set up, the working logic of each inlet or outlet, on the main card according to<br />
the following correspondences:<br />
Digital inlets<br />
N.C. during the normal working of the unit the contact is closed (logic state 0), the contact<br />
opening, involves an action from the program (logic state 1)<br />
N.O. during the normal working of the unit the contact is opened (logic state 0), the contact<br />
closing, involves an action from the program (logic state 1)<br />
Digital outlets<br />
N.C. the activation of a loading connected to the card pCO1OEM is caused from a closing of an<br />
associated contact (references to the inlet/outlet tables)<br />
N.O. the activation of a loading connected to the card pCO1OEM is caused from an opening of an<br />
associated contact (references to the inlet/outlet tables)<br />
2.7 B4 multifunction analogue inlet<br />
The management of the B4 analogue inlet provides distinct modalities if is qualified or no, the heat<br />
recovery function and the compensation of the adjusting setpoint based on the values of the<br />
outside temperature.<br />
The following table summarises the correspondences between the analogue inlet functionality and<br />
particular unit enabled functions.<br />