07.11.2014 Views

Tender Document Volume - 2 - BPDB

Tender Document Volume - 2 - BPDB

Tender Document Volume - 2 - BPDB

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

6. Sump tank<br />

The sump tank allows draining liquid fuel from combustion system and from<br />

exhaust plenum when there is false start. It may be preassembled and includes<br />

the followings<br />

-One tank of 1 m 3 capacity<br />

-One manual pump<br />

Gas Fuel System<br />

FUEL GAS HANDLING FACILITIES<br />

SCOPE OF WORK<br />

The Contractor shall design, manufacture, inspect, test, delivery to the site and<br />

install of natural gas handling facilities with all accessories as specified hereunder<br />

for the plant.<br />

The gas turbine unit shall be furnished with a complete gas fuel system. The gas<br />

handling system including Gas Booster Compressor shall also be provided.<br />

NATURAL GAS SUPPLY SYSTEM<br />

To forward the natural gas from the main gas supply header to the gas turbine<br />

unit and to adjust its supply pressure to normal operating pressure, the<br />

Contractor shall furnish one (1) complete factory assembled skid mounted gas<br />

pressure regulating unit including all accessories and necessary pipe connections<br />

to the BOARD's gas supply header for gas turbine unit.<br />

Each gas handling unit shall comprise at least the following major items:<br />

Gas Booster Compressors (one running and one standby, each having capacity for<br />

meeting total gas requirement at all ambient temperatures with 10% margin)<br />

with necessary sealing, cooling, anti-surge device, proven control system etc.<br />

Inlet strainer<br />

A flow meter with bypass system and with integration<br />

Pressure gauges<br />

Pressure regulating equipment<br />

Safety valve and relief valve<br />

A gas conditioner (scrubber, separator and others as required)<br />

Other equipment for satisfactory completion of the work.<br />

Each unit shall have guaranteed capacity, which matches or exceeds the gas<br />

turbine needs under all load operating conditions at site conditions.<br />

Specification of natural gas is shown on Appendix (Vol 2 of 3)<br />

3.3.2.8 Air Inlet System<br />

The air filtration arrangement shall be multi stage (pre-filter and high efficiency).<br />

Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)<br />

28

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!