on the transformer.<br />
The wiring shall be connected at the terminal blocks terminating the outgoing<br />
control cable. The flexible tube of the vapour tension thermometer shall be<br />
covered by a protective tube.<br />
(8) Insulating oil<br />
The insulating oil shall have a sufficient insulation strength, and shall be excellent<br />
in heat conductivity, low in viscosity and pour point, and high in flash point. The<br />
oil shall not cause any corrosion to insulating materials and structured materials of<br />
electrical equipment and shall be chemically stable for long years of use.<br />
Delivery shall be made to Site partly contained in the transformers and partly in<br />
steel drums, according to the method of packing employed. An excess of 10% of<br />
the quantity of oil required for filling transformers shall also be supplied and its<br />
cost shall be included in the price of each transformer.<br />
(9) Skid Base<br />
The transformer shall be provided with a skid base with four (4) steel wheels and<br />
necessary jacks for setting and appropriate devices for locking in position of its<br />
foundation.<br />
5.2 GENERATOR STEP-UP TRANSFORMERS<br />
5.2.1 TYPE AND RATIO<br />
The transformer shall be of single phase, oil immersed, self cooled / forced air<br />
cooled (ONAN/ONAF) by cooling fans, outdoor use type. Ratio of delta star<br />
connection shall be 11 KV to 230 KV on full load condition.<br />
The connection of the three phase bank shall be arranged in vector symbol Ynd11<br />
according to IEC 74-4 and neutral of star connected high tension winding shall be<br />
solidly grounded.<br />
The on load tap changer shall be provided on the high tension winding, and their<br />
ratio shall be as follows:<br />
230 kV(±1.25% x 8)<br />
5.2.2 OUTPUT AND REQUIRED NUMBERS<br />
The maximum continuous rating of the transformer shall met at any taps a total<br />
output of the generator which is connected with the transformer in series as<br />
shown in the attached single line diagram.<br />
The self cooled capacity shall not be less than 75 % of forced air cooled capacity.<br />
5.2.3 IMPEDENCE VOLTAGE<br />
Impedance voltage (+ve seq.) shall be within the range of 15% to 18% on the<br />
forced air cooled rating on the rated tapping (11/230 KV ) and shall be<br />
guaranteed by the Contractor.<br />