Power Frequency (rms.)<br />

(For 1 mm.)<br />

: 22 KV<br />

3) The rated service voltage shall be of 6.6 KV.<br />

4) The current rating of the main bas bars shall not less than the rating of<br />

the unit auxiliary transformer and rating of the associated connections shall be<br />

determined by the Contractor.<br />

(5) The short time three phase fault level rating for one second of the switch<br />

gear shall be of 40KA (rms).<br />

4.4.3 Construction And Fittings<br />

The 6.6 KV common switchgear shall be designed and constructed as same as<br />

those for 15 KV generator switchgear specified in Section 4.3.<br />

4.4.4 Circuit Breaker<br />

The circuit breaker shall be of SF 6 gas or vacuum type.<br />

The circuit breaker shall comply with the requirements of IEC 56 and with the<br />

relevant requirements of this specification.<br />

All circuit breakers shall be identical in arrangement and shall be interchangeable.<br />

- Rated Voltage : 6.6 KV<br />

- Rated Current : 1250A<br />

- Interrupting Current : 40 KA (rms)<br />

Only fully type tested circuit breakers complying with IEC 56 will be considered,<br />

and a statement as to the availability of certificates of all such type tests including<br />

impulse tests on identical or similar circuit breakers shall be submitted with<br />

<strong>Tender</strong>.<br />

4.4.5 Composition Of Cubicles<br />

(1) Incoming Circuit Breaker Cubicle for unit(s)<br />

- Circuit breaker : One(1)<br />

1250 A, 40 KA (rms)<br />

- Current transformer :Three(3) units<br />

600/300- 5A, 40 VA<br />

- End terminal :One(1) lot<br />

- Ammeter with selector switch :One(1) set<br />

- Protective relays :One (1) set<br />

- Control switch, etc. :One(1) lot<br />

Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)<br />