a. Temperature detector (Refer to Clause 4.1.10)<br />

- normal use :more than 6 (six)<br />

-Spare<br />

:more than three(3)<br />

b. Thermometers and thermocouples at bearing drain of generator and<br />

exciter bearings, and at any other location required for operation monitor.<br />

c. Pressure gauge at bearing oil feed, and at any other location required<br />

for operation.<br />

d. Alarm contacts<br />

e. Spare heater<br />

The stator shall be equipped with space heater. During the generator stop, the<br />

space heater shall be in service automatically.<br />

f. Other<br />

Other instrument, terminal box, hardware buried into the generator foundation<br />

and all other necessary accessories for generator.<br />

4.2 Exciter And Automatic Voltage Regulator<br />

4.2.1 Exciter<br />

A complete voltage regulating and excitation system shall be provided. A complete<br />

and details description of the proposed system that meets the requirements of<br />

these specification shall be submitted with the <strong>Tender</strong>.<br />

A shaft mounted brushless type with static type control shall be provided.<br />

The excitation system shall match the generator rating and shall maintain the<br />

voltage of the unit within a tolerance of plus and minus 0.5% of rated voltage<br />

regulation. The exciter shall have capacity to supply not less than 110% of the<br />

field current required by the generator at rated output, power factor, frequency<br />

and voltage.<br />

The rated voltage of the exciter shall be 110% of the machine excitation voltage<br />

at the rated output of the machine.<br />

The ceiling voltage of the exciter shall not be less than 140% of the matching<br />

excitation voltage. Insulation of stator and rotor winding of the exciter shall be<br />

class F. A field breaker and discharge resistance shall be provided or alternatively<br />

special provisions must be taken to either discharge or suppress excitation<br />

following generator fault.<br />

The excitation system shall have ample capacity to permit operation throughout<br />

its capability up to over-excitation and under-excitation limit as shown in the<br />

manufacturer's capability curves.<br />

Over excitation limiter and under excitation limiter shall be provided.<br />

Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)<br />

36