3WL Air Circuit Breakers<br />

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)<br />

General data<br />

ETU15B electronic release<br />

Mechanical RESET<br />

<strong>for</strong> reclosing lockout<br />

and mechanical<br />

tripped indicator<br />

Indicator: overcurrent<br />

release activated<br />

Indicator: overload alarm<br />

Rotary switch <strong>for</strong> setting<br />

value, overload release<br />

Rotary switch <strong>for</strong> setting<br />

value, instantaneous<br />

short-circuit release<br />

Option: safety lock<br />

prevents pressing of<br />

reset button after<br />

overcurrent release<br />

Indicator: fault in<br />

overcurrent release<br />

Sealing ring<br />

Application:<br />

Simple building and system<br />

protection without time-selective<br />

coordination up to 4000 A. Not to<br />

be used <strong>for</strong> size III.<br />

Features:<br />

• Adjustable overload protection<br />

with I 2 t characteristic curve<br />

with preset delay time<br />

t R = 10 seconds at 6 × I R<br />

• Instantaneous short-circuit protection<br />

adjustable in the range<br />

2 ... 8 × I n<br />

• Overload display<br />

• Protection function is set by<br />

means of the rotary coding<br />

switch<br />

NSE0_00954b<br />

Test socket<br />

For technical details see the table<br />

"Functional Overview of the<br />

Electronic Release System"<br />

under "Technical Specifications".<br />

ETU25B electronic release<br />

Mechanical RESET<br />

<strong>for</strong> reclosing lockout<br />

and mechanical<br />

tripped indicator<br />

Indicator: overcurrent<br />

release activated<br />

Indicator: overload alarm<br />

Rated current module<br />

Rotary switch <strong>for</strong> setting<br />

value, overload release<br />

Rotary switch <strong>for</strong> setting<br />

value, instantaneous<br />

short-circuit release<br />

Short-circuit protection<br />

fixed setting<br />

Query pushbutton<br />

Test pushbutton<br />

Rating Plug<br />

ETU25B<br />

NSE0_00955b<br />

Option: safety lock<br />

prevents pressing of<br />

reset button after<br />

overcurrent release<br />

Indicator: fault in<br />

overcurrent release<br />

Indicator: cause of release<br />

Rotary switch <strong>for</strong> delay,<br />

short-circuit release<br />

Sealing ring<br />

Clear pushbutton<br />

Test socket<br />

Application:<br />

Classical building, motor and system<br />

protection with time-selective<br />

coordination <strong>for</strong> up to 6300 A<br />

Features:<br />

• Adjustable overload protection<br />

with I 2 t- characteristic curve<br />

Delay time<br />

t R = 10 seconds at 6 × I R<br />

• Short-time delayed short-circuit<br />

protection adjustable in the<br />

range 1.25 ... 12 × I n and<br />

• Instantaneous short-circuit protection<br />

preset<br />

to 20 × I n , max. 50 kA<br />

• Can be adapted at any time to<br />

the required plant currents<br />

through retrofittable rated current<br />

module,<br />

thus ensuring overload protection<br />

in the range from 100 A to<br />

6300 A.<br />

• Overload display<br />

• Indicates the reason <strong>for</strong> tripping<br />

by means of an LED<br />

• Test facility <strong>for</strong> the release<br />

• Protection functions are<br />

set by means of the<br />

rotary coding switch<br />

For technical details see the table<br />

"Functional Overview<br />

of the Electronic Release System"<br />

under "Technical Specifications".<br />