3WL Air Circuit Breakers<br />

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)<br />

Project planning aids<br />

© <strong>Siemens</strong> AG 2011<br />

Door cutout <strong>for</strong> operator panel using protective cover IP55<br />

Protective cover, IP55<br />

NSE0_01029c<br />

4 x R5<br />

4 x 5,5<br />

400<br />

395<br />

NSE0_01030b<br />

85<br />

295-300<br />

70<br />

68<br />

72 72<br />

340-350<br />

435<br />

Circuit breaker mounting level<br />

341<br />

Mounting surface <strong>for</strong> circuit breaker<br />

or guide frame<br />

313<br />

17<br />

Circuit breaker<br />

mounting level<br />

148<br />

Safety clearance from grounded parts<br />

Rated operational voltage Above<br />

auxiliary connector<br />

V/AC<br />

mm<br />

Lateral<br />

(each side)<br />

mm<br />

Size I, fixed-mounted version<br />

500 75 1) 0 0<br />

690 75 1) 0 0<br />

Size I, withdrawable version,<br />

without arc chute cover<br />

500 50 1) 0 0<br />

690 50 1) 0 0<br />

Size I, withdrawable version,<br />

with arc chute cover<br />

500 0 0 2) 0<br />

690 0 0 2) 0<br />

Size II, fixed-mounted version<br />

500 75 1) 0 0<br />

690 75 1) 0 0<br />

1000 180 0 0<br />

Size II, withdrawable version,<br />

without arc chute cover<br />

500 50 1) 0 0<br />

690 50 1) 0 0<br />

1000 100 0 0<br />

Size II, withdrawable version,<br />

with arc chute cover<br />

500 0 0 2) 0<br />

690 0 0 2) 0<br />

Size III, fixed-mounted version<br />

500 75 1) 0 0<br />

690 75 1) 0 0<br />

1000 180 0 0<br />

Size III, withdrawable version,<br />

without arc chute cover<br />

500 50 1) 0 0<br />

690 50 1) 0 0<br />

1000 100 0 0<br />

Size III, withdrawable version,<br />

with arc chute cover<br />

500 0 0 2) 0<br />

690 0 0 2) 0<br />

DC non-automatic air circuit breakers<br />

300 45 0 0<br />

600 200 0 0<br />

1000 150 0 0<br />

Rear<br />

All safety clearances above the circuit breaker refer to the upper<br />

edge of the auxiliary connector - not to the upper edge of the arc<br />

chute! See dimensional drawings on pages 39 to 47, Parts 4)<br />

and 5).<br />

mm<br />

Safety clearances from live parts<br />

Rated operational voltage Above<br />

auxiliary connector<br />

V/AC<br />

mm<br />

1)<br />

2)<br />

3)<br />

4)<br />

Value <strong>for</strong> plate; 0 mm <strong>for</strong> struts and grids<br />

Lateral<br />

(each side)<br />

mm<br />

Rear<br />

40 mm (size II: 70 mm) <strong>for</strong> plates, which cover the lateral openings in the<br />

guide frame<br />

Not <strong>for</strong> switching capacity S.<br />

For switching capacity S: 100 mm.<br />

mm<br />

Size I, fixed-mounted version<br />

500 150 20 20<br />

690 300 50 125<br />

1000 500 3) 100 3) 140 3)<br />

Size I, fixed-mounted version,<br />

with arc chute cover<br />

500 14 50 4) 14<br />

690 14 225 4) 14<br />

Size I, withdrawable version,<br />

without arc chute cover<br />

500 150 20 14<br />

690 300 50 14<br />

1000 500 3) 100 3) 140 3)<br />

Size I, withdrawable version,<br />

with arc chute cover<br />

500 14 100 14<br />

690 14 100 14<br />

Size II, fixed-mounted version<br />

500 250 50 20<br />

690 600 100 140<br />

1000 430 100 125<br />

Size II, withdrawable version,<br />

without arc chute cover<br />

500 250 50 14<br />

690 600 100 30<br />

1000 350 100 14<br />

Size II, withdrawable version,<br />

with arc chute cover<br />

500 14 50 14<br />

690 14 225 14<br />

Size III, fixed-mounted version<br />

500 75 20 20<br />

690 500 100 125<br />

1000 430 100 125<br />

Size III, withdrawable version,<br />

without arc chute cover<br />

500 50 20 14<br />

690 500 100 14<br />

1000 350 100 14<br />

Size III, withdrawable version,<br />

with arc chute cover<br />

500 14 50 14<br />

690 14 200 14<br />

38 <strong>Siemens</strong> · <strong>2012</strong>