Configuration Manual for Catalog LV 10.1 · 2012 - Siemens
Configuration Manual for Catalog LV 10.1 · 2012 - Siemens
Configuration Manual for Catalog LV 10.1 · 2012 - Siemens
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
3WL Air Circuit Breakers<br />
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)<br />
Project planning aids<br />
© <strong>Siemens</strong> AG 2011<br />
■ Characteristic curves 2)<br />
Every release type and every setting has its own characteristic<br />
curve. Only a selection is shown in the following. The characteristic<br />
curves each show the largest and smallest setting range of<br />
3WL circuit breakers with 1000 A rated current at 500 V rated<br />
voltage with various releases. In order to obtain a complete tripping<br />
characteristic, the relevant parts of the characteristics have<br />
to be combined. The characteristic curves show the behavior of<br />
the release when it is activated by a current that is already flowing<br />
be<strong>for</strong>e the tripping operation. If the overcurrent tripping occurs<br />
immediately after switch on and the release is there<strong>for</strong>e not<br />
yet enabled, the opening time is extended, depending on the<br />
level of the overcurrent by up to 15 ms. In order to determine the<br />
break-times of the circuit breakers, approximately 15 ms must<br />
be added to the opening times shown <strong>for</strong> the arcing time.<br />
Refer to the following legend <strong>for</strong> tolerances.<br />
The characteristic curves shown apply to ambient temperatures<br />
at the circuit breaker between -5 and +55 °C. The release can<br />
be operated at ambient temperatures of -20 to +70°C.<br />
An extended tolerance band can apply at these temperatures.<br />
[s]<br />
Opening time<br />
10000<br />
1000<br />
100<br />
10<br />
R min<br />
0,4 ... 1,0 x n<br />
R max<br />
1<br />
sd min<br />
1,25 ... 12 x n<br />
sd max<br />
sd max<br />
0,1<br />
0 ... 0,4 s sd min<br />
i i > 20 x n<br />
max. 50 kA<br />
0,01<br />
0,1 1 10 100<br />
/ n<br />
3WL circuit breaker with ETU25B release,<br />
LSI characteristic curve<br />
[s]<br />
Opening time<br />
10000<br />
1000<br />
100<br />
10<br />
g min<br />
g max<br />
NSE0_01520<br />
NSE0_01521<br />
[s]<br />
Opening time<br />
10000<br />
1000<br />
100<br />
10<br />
1<br />
0,1<br />
0,01<br />
0,1 1 10 100<br />
/ n<br />
3WL circuit breaker with ETU15B release<br />
[s]<br />
Opening time<br />
R min<br />
R max<br />
0,5 ... 1,0 x n<br />
i min<br />
2 ... 8 x n<br />
3WL circuit breaker with ETU27B release,<br />
LSIN characteristic curve<br />
[s]<br />
Opening Time<br />
10000<br />
1000<br />
100<br />
10<br />
1<br />
0,1<br />
i max<br />
0,01<br />
0,1 1 10 100<br />
/ n<br />
10000<br />
1000<br />
100<br />
10<br />
R min<br />
0,4 ... 1,0 x n<br />
N<br />
sd min<br />
R max<br />
1,25 ... 12 x n<br />
sd<br />
0 ... 0,4 s<br />
sd max<br />
2 sd = const<br />
i<br />
sd max<br />
sd min<br />
i > 20 x n<br />
max. 50 kA<br />
NSE0_01527<br />
NSE0_01519<br />
NSE0_01523a<br />
1,25 ... 12 x n<br />
2 sd<br />
1<br />
0,1<br />
100 ... 1200 A 1) 0,1 ... 0,5 s<br />
g max<br />
g min<br />
0,01<br />
100 1000 10000 100000<br />
A<br />
3WL circuit breaker with ETU27B release,<br />
G characteristic curve<br />
Tolerances <strong>for</strong> the set currents<br />
L: Tripping operations between 1.05 and 1.2 x I R<br />
S: –0 %, +20 %<br />
I: –0 %, +20 %<br />
G: –0 %, +20 %<br />
Tolerances <strong>for</strong> the tripping times<br />
L: –20 %, +0 % <strong>for</strong> I 2 t characteristic curve<br />
S: –0 %, +60 ms or -0 %, 10 % <strong>for</strong> tripping times greater than 600 ms<br />
I: