Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, SF6-<strong>Insulated</strong><br />

Design<br />

Double-busbar panel design<br />

Features<br />

• Stainless-steel module of<br />

circuit-breaker and busbar<br />

• Sendzimir-galvanized sheetsteel<br />

enclosure<br />

• Self-supporting structure<br />

• Electrical connections via<br />

cast-resin insulated, screened<br />

and bolted module couplings<br />

• Low-voltage compartment<br />

can be removed without<br />

interrupting the bus wires<br />

• Degree of protection<br />

– IP 65 for primary parts<br />

– IP 3XD for secondary parts<br />

• Lateral metallic cable ducts<br />

for control cables<br />

• Suitable for connecting<br />

single and three-core cables<br />

as well as bars<br />

• Circuit-breaker module replacement<br />

without gas work<br />

and without interrupting<br />

busbar operation<br />

• Instrument transformers can<br />

be removed without changing<br />

the positions of busbar<br />

and circuit-breaker modules<br />

• Instrument transformers can<br />

be removed without gas work<br />

(located outside the gas compartments)<br />

• Maintenance-free vacuum<br />

circuit-breaker under normal<br />

ambient conditions according<br />

to IEC 60694 / VDE 0670,<br />

Part 1000<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

NX PLUS<br />

HA35-2401b eps<br />

1 Door of low-voltage compartment<br />

2 Mimic diagram<br />

3 Multifunction protection relay<br />

SIPROTEC 4 type 7SJ61/ 7SJ62<br />

for protection and control<br />

4 EMERGENCY-OFF pushbutton,<br />

mechanical<br />

5 Door to mechanical control board<br />

6 Cover of connection compartment<br />

7 Busbar cover<br />

8 Busbar module (2x), welded,<br />

SF 6 -insulated<br />

9 Rupture diaphragm<br />

10 Three-pole busbar system (2x)<br />

11 Three-position disconnector,<br />

SF 6 -insulated, with the three switch<br />

positions:<br />

CLOSED – OPEN – READY-TO-EARTH<br />

12 Module coupling between busbar<br />

module and circuit-breaker module<br />

13 Circuit-breaker module, welded,<br />

SF 6 -insulated, with integrated cable<br />

connection<br />

14 Vacuum interrupter of circuit-breaker<br />

15 Pressure relief duct<br />

16 Integrated cable connection as<br />

inside cone<br />

17 Low-voltage compartment,<br />

standard: 935 mm high,<br />

option: 1100 mm high<br />

18 Ring-core current transformer,<br />

normal or oval design<br />

19 Manual and motor operating<br />

mechanism of three-position<br />

disconnector<br />

7<br />

8<br />

10<br />

9<br />

11<br />

12<br />

13<br />

14<br />

9<br />

15<br />

16<br />

9<br />

25<br />

31<br />

26<br />

9<br />

27<br />

9<br />

13<br />

31<br />

28<br />

29 23<br />

9<br />

13<br />

16<br />

31<br />

30<br />

Panel with integrated inside cone<br />

Panel with separate inside cone<br />

Panel with outside cone<br />

Panel with integrated inside cone and current<br />

transformers in the cable connection compartment<br />

17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

23<br />

24<br />

24<br />

22<br />

24<br />

22<br />

23<br />

24<br />

14 <strong>Siemens</strong> HA 35.51 · 2003