Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, SF6-<strong>Insulated</strong><br />
Standards<br />
Standards, specifications, guidelines<br />
Current-carrying capacity<br />
• According to IEC 60 298 / VDE<br />
0670 Part 6 or IEC 60 694 /<br />
VDE 0670 Part 1000, the rated<br />
normal current refers to the<br />
following ambient temperatures:<br />
– Maximum value<br />
of 24-h mean + 35 °C<br />
– Maximum value + 40 °C<br />
• The current-carrying capacity<br />
of the panels and busbars depends<br />
on the ambient temperature<br />
outside the enclosure.<br />
Tests for resistance to internal<br />
arc faults<br />
• Tests for verifying resistance to<br />
internal arc faults should establish<br />
proper protection for<br />
operating personnel<br />
• Tests for resistance to internal<br />
arc faults can be agreed<br />
between the owner and<br />
manufacturer in accordance<br />
with IEC 60 298 / VDE 0670<br />
Part 6<br />
• All criteria of the above<br />
standards are met<br />
Resistance to internal<br />
arc faults<br />
Due to the single-pole enclosure<br />
of external components and<br />
the SF 6 -insulation of switching<br />
devices, the probability of faults<br />
in NXPLUS fixed-mounted<br />
circuit-breaker switchgear is<br />
considerably lower than in<br />
former switchgear types, as<br />
• There are no effects due to<br />
external influences such as<br />
– Pollution layers<br />
– Moisture<br />
– Small animals and foreign<br />
bodies<br />
• Maloperation is practically<br />
excluded by logical arrangement<br />
of the operating<br />
mechanism elements<br />
• The three-position disconnector<br />
and the vacuum<br />
circuit-breaker provide<br />
short-circuit-proof earthing<br />
of the feeder<br />
Should arcing occur in spite of<br />
this, the pressure is relieved towards<br />
the rear into a duct.<br />
In the unlikely event of a fault<br />
inside the module vessel, the<br />
energy conversion in the case<br />
of an internal arc fault is minor<br />
thanks to the SF 6 -insulation,<br />
i.e.approximately only ½3<br />
compared<br />
to air. The pressure relief<br />
in the rear wall of the module<br />
vessel operates in the range<br />
of 2 to 3.5 bar. The escaping<br />
gases are discharged to the<br />
rear into a duct.<br />
The pressure relief duct diverts<br />
the gases upwards.<br />
Aseismic capacity (optional)<br />
NXPLUS switchgear can be upgraded<br />
for regions at risk from<br />
earthquakes.<br />
For upgrading, earthquake<br />
qualification testing has been<br />
carried out in accordance with<br />
the following standards:<br />
• IEC 68-3-3, 1993<br />
• IEC 68-2-6, 1995<br />
• IABG TA13-TM-002/98<br />
(guide)<br />
Within the range of the prevailing<br />
earthquake frequencies<br />
from1Hzto35Hz,the<br />
category 1 required response<br />
spectrum according to IABG<br />
TA13-TM-002/98 covers the<br />
following response spectra:<br />
• Uniform Building<br />
Code zone 3<br />
• Seismic Requirements<br />
Spec. 9067; Department of<br />
Water & Power, Los Angeles<br />
• GTS – 1.013 ENDESA, Chile<br />
• VDE 0670 Part 111<br />
<strong>Siemens</strong> HA 35.51 · 2003<br />