The capacity expansion in existing 10G environments<br />

The standards TIA-942, DIN EN 50173-5 and ISO/IEC 24764 provide specifications for network planning in data<br />

centers. The steps below assume a correspondingly well-planned and installed network and merely describe the<br />

migration to 100 GbE.<br />

The first step in the migration from 10 GbE to 40/100 GbE certainly involves the expansion of capacity in an<br />

existing 10 GbE environment. A 12-fiber MPO cable serves as the permanent link (backbone). MPO modules and<br />

patch cords establish the connection to the 10G switches.<br />

Different constellations emerge depending on the legacy infrastructure and the polarity method used.<br />

Methode A<br />

10G, Case 1 - an MPO trunk cable (type A, male-male) serves as the permanent link (middle). MPO modules (type A, female)<br />

provide the transition to the LC Duplex patch cords A-to-B (left) and A-to-A (right).<br />

10G, Case 2 - an MPO trunk cable (type A, male-male) serves as the permanent link (middle). An MPO module (type A,<br />

female) provides the transition to LC Duplex patch cord A-to-B (left), adapter plate (type A) and harness cable (female) as an<br />

alternative to the combination of MPO module and LC Duplex patch cord.<br />

10G, Case 3 - duplex connection without permanent link, consisting of LC Duplex patch cord A-to-B (left), MPO module<br />

(type A, female) and harness cable (male).<br />

Methode R<br />

10G - an MPO trunk cable (type B, male-male) serves as a permanent link (middle), MPO modules (type R, female) provide<br />

the transition to the LC Duplex patch cords A-to-B (left, right).<br />

Important: Harness cables cannot be used with method R!<br />

The capacity expansion from 10G to 40G<br />

If the next step involves replacing the 10G switches with 40G versions, MPO adapter plates can be installed easily<br />

instead of the MPO modules to make the next adaptation.<br />

Here, too, the installer has to keep in mind the polarity method used.<br />

Methode A<br />

Replacement of the MPO modules (type A) with MPO adapter plates (type A) and the LC Duplex patch cords with MPO patch<br />

cords type A, female-female (left) and type B, female-female (right). The permanent link (type A, male-male) remains.<br />