The capacity expansion in existing 10G environments<br />
The standards TIA-942, DIN EN 50173-5 and ISO/IEC 24764 provide specifications for network planning in data<br />
centers. The steps below assume a correspondingly well-planned and installed network and merely describe the<br />
migration to 100 GbE.<br />
The first step in the migration from 10 GbE to 40/100 GbE certainly involves the expansion of capacity in an<br />
existing 10 GbE environment. A 12-fiber MPO cable serves as the permanent link (backbone). MPO modules and<br />
patch cords establish the connection to the 10G switches.<br />
Different constellations emerge depending on the legacy infrastructure and the polarity method used.<br />
Methode A<br />
10G, Case 1 - an MPO trunk cable (type A, male-male) serves as the permanent link (middle). MPO modules (type A, female)<br />
provide the transition to the LC Duplex patch cords A-to-B (left) and A-to-A (right).<br />
10G, Case 2 - an MPO trunk cable (type A, male-male) serves as the permanent link (middle). An MPO module (type A,<br />
female) provides the transition to LC Duplex patch cord A-to-B (left), adapter plate (type A) and harness cable (female) as an<br />
alternative to the combination of MPO module and LC Duplex patch cord.<br />
10G, Case 3 - duplex connection without permanent link, consisting of LC Duplex patch cord A-to-B (left), MPO module<br />
(type A, female) and harness cable (male).<br />
Methode R<br />
10G - an MPO trunk cable (type B, male-male) serves as a permanent link (middle), MPO modules (type R, female) provide<br />
the transition to the LC Duplex patch cords A-to-B (left, right).<br />
Important: Harness cables cannot be used with method R!<br />
The capacity expansion from 10G to 40G<br />
If the next step involves replacing the 10G switches with 40G versions, MPO adapter plates can be installed easily<br />
instead of the MPO modules to make the next adaptation.<br />
Here, too, the installer has to keep in mind the polarity method used.<br />
Methode A<br />
Replacement of the MPO modules (type A) with MPO adapter plates (type A) and the LC Duplex patch cords with MPO patch<br />
cords type A, female-female (left) and type B, female-female (right). The permanent link (type A, male-male) remains.<br />
R&M <strong>Data</strong> <strong>Center</strong> <strong>Handbook</strong> V2.0 © 08/2011 Reichle & De-Massari AG Page 133 of 156