R&M Data Center Handbook
R&M Data Center Handbook
R&M Data Center Handbook
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
www.datacenter.rdm.com<br />
Results in accordance with EN 61000-4-4 (left) / Results operational test “mesh cable tray” (right)<br />
The figure left shows the results of this test. All shielded systems allow the use of 10GBase-T in all environmental<br />
conditions (E1, E2, E3). At the same time, higher quality shielding provided better immunity against fast transients.<br />
High-quality unshielded cabling allows the use of 1000Base-T in an office environment. For an industrial environment<br />
and for 10GBase-T, shielded cabling is necessary. Unshielded cabling, if it is to support 10GBase-T, needs<br />
additional protective measures such as the careful separation of the data cables from the power cables.<br />
A double-sided ground improves the immunity of shielded cabling against external fast transients above the<br />
minimum requirements of the standard. If the shield is not continuous, its effectiveness with 10GBase-T is<br />
negated, and the protection is then the same as with unshielded cabling. At lower frequencies (such as used in<br />
1000Base-T), a certain protective effect of the non-continuous shield is apparent, especially with double-sided<br />
grounding.<br />
An operational test with fluorescent lamps that were located 0.5 m from the data cable showed that the test<br />
conditions in the test based on the standard were entirely realistic. The interference that arises when a fluorescent<br />
lamp is switched on influenced the 10GBase-T data transmission in the same way as during the test according to<br />
the standard. Not only the lamp itself, but also the power cable to it, created interference. It must therefore be<br />
ensured that there is sufficient separation of both from the data cabling.<br />
In order to compare the standard test using the coupling clamp to an actual installation situation, the “mesh cable<br />
tray” experiment was also carried out. The data cables and a power cable were laid in a mesh cable tray with a<br />
total length of 30 m and with a constant separation from 0 to 50 cm. The interference signal according to the standard<br />
was then applied to the power cable. The figure shows the results of these measurements. A comparison of<br />
the results with those of the test according to the standard from the figure shows that the standardized test<br />
simulates a separation of the cables of approximately 1 - 2 cm. In order to guarantee the operation of 10GBase-T,<br />
a separation between the data and power cables of at least 30 cm must be maintained with an unshielded system.<br />
The shielded cabling met the requirements even without any separation between the cables.<br />
According to EN 50174-2, a separation of only 2 cm is defined for the unshielded system in this configuration,<br />
which however is insufficient for 10GBase-T. In other words, with unshielded cables, when using 10GBase-T, a<br />
far greater separation must be maintained than is defined in the standard.<br />
A further test in accordance with EN 61000-4-6 was carried out to check the system’s immunity against conducted<br />
RF interference in the range from 150 kHz to 80 MHz on power cables located nearby. Power cables can act as<br />
antennas for high-frequency interference coming from external sources (such as shortwave and VHF transmitters)<br />
or also intentionally subjected to a powerline signal. In this test, too, the previously mentioned coupling clamp was<br />
used. The stress levels were chosen in accordance with the MICE table (see Figure, “Conducted high frequency”).<br />
The results corresponded to the well-known pattern that the shielded cabling meets all requirements for 10GBase-<br />
T. Unshielded cabling meets the requirements for offices and areas with light industry for 1000Base-T, however<br />
for 10GBase-T transmissions additional protective measures such as increased separation of the data cabling<br />
from power cabling is necessary.<br />
Immunity from magnetic fields arising from power cables<br />
This test in accordance with EN61000-4-8 checks the ability of a system to function in the presence of strong<br />
magnetic fields at 50 Hz. These magnetic fields can be generated by power lines (cable or busbars) or powerdistribution<br />
equipment (transformers, distribution panels). The stress levels were selected in accordance with the<br />
MICE table (see Figure, “Magnetic fields”). All cabling fulfills the highest environmental class (E3) with both<br />
1000Base-T and 10GBase-T. No difference was determined between the susceptibility of shielded or unshielded<br />
cabling. No heightened susceptibility of the shielded cabling based on ground loops can be observed.<br />
R&M <strong>Data</strong> <strong>Center</strong> <strong>Handbook</strong> V2.0 © 08/2011 Reichle & De-Massari AG Page 153 of 156