3.2. <strong>Data</strong> <strong>Center</strong> Layout<br />

In spite of the virtualization trends currently in the software market – keyword server consolidation – there is a high<br />

demand on the horizon for renewing data center and server rooms. It is estimated that over 85 percent of all data<br />

centers in Germany are over ten years old. A study by Actionable Research that was recently commissioned by<br />

Avocent, is also examining the global situation in this area. Approximately 35 percent of all data centers worldwide<br />

are therefore currently undergoing a redesign.<br />

3.2.1. Standard Requirements<br />

Even if small differences between generic and data center cabling are uncovered between the American TIA-942<br />

standard and international and European standards, these bodies of standards essentially differ only in how they<br />

name functional elements.<br />

ISO/IEC 24764 ISO 11801 TIA-942<br />

External Network Interface (ENI)<br />

[Externe Netzschnittstelle (ENS)]<br />

Campus Distributor (CD)<br />

[Standortverteiler (SV)]<br />

ENI (External Network Interface)<br />

ER (Entrance Room)<br />

Network Access Cable<br />

[Netzzugangkabel]<br />

Primary Cable [Primärkabel]<br />

Backbone Cabling<br />

Main Distributor (MD)<br />

[Hauptverteilter (HV)]<br />

Building Distributor (BD)<br />

[Gebäudeverteiler (GV) ]<br />

MC (Main Cross Connect)<br />

MDA (Main Distribution Area)<br />

Main Distributor Cable<br />

[Hauptverteilerkabel]<br />

Secondary Cable [Sekundärkabel ] Backbone Cabling<br />

Zone Distributor (ZD)<br />

[Bereichsverteiler (BV)]<br />

Floor Distributor (FD) [Etagenverteiler<br />

(EV)]<br />

HC (Horizontal Cross Connect)<br />

HDA (Horizontal Distribution Area)<br />

Zone Distributor Cable<br />

Tertiary/Horizontal Cable [Tertiär-<br />

[Bereichsverteilungskabel] /Horizontalkabel]<br />

Horizontal Cabling<br />

Local Distribution Point (LDP)<br />

[Lokaler Verteilpunkt (LVP)]<br />

Consolidation Point (CP) [Sammelpunkt<br />

(SP)]<br />

CP* (Consolidation Point)<br />

ZDA (Zone Distribution Area)<br />

Local Distribution Point Cable Consolidation Point Cable<br />

[Lokales Verteilpunktkabel] [Sammelpunktkabel]<br />

Horizontal Cabling<br />

Equipment Outlet (EO)<br />

[Geräteanschluss (GA)]<br />

Telecommunications Outlet (TO)]<br />

[Informationstechnischer Anschluss (TA)<br />

EO (Equipment Outlet)<br />

EDA (Equipment Distribution Area)<br />

Unique assignment exists of functional elements to rooms, though in the TIA-942 it is data center areas rather<br />

than the functional elements that are at the forefront. Given a detailed examination, we see that this topology is<br />

the same for ISO/IEC 24764 and EN 50173-5.<br />