3.2. <strong>Data</strong> <strong>Center</strong> Layout<br />
In spite of the virtualization trends currently in the software market – keyword server consolidation – there is a high<br />
demand on the horizon for renewing data center and server rooms. It is estimated that over 85 percent of all data<br />
centers in Germany are over ten years old. A study by Actionable Research that was recently commissioned by<br />
Avocent, is also examining the global situation in this area. Approximately 35 percent of all data centers worldwide<br />
are therefore currently undergoing a redesign.<br />
3.2.1. Standard Requirements<br />
Even if small differences between generic and data center cabling are uncovered between the American TIA-942<br />
standard and international and European standards, these bodies of standards essentially differ only in how they<br />
name functional elements.<br />
ISO/IEC 24764 ISO 11801 TIA-942<br />
External Network Interface (ENI)<br />
[Externe Netzschnittstelle (ENS)]<br />
Campus Distributor (CD)<br />
[Standortverteiler (SV)]<br />
ENI (External Network Interface)<br />
ER (Entrance Room)<br />
Network Access Cable<br />
[Netzzugangkabel]<br />
Primary Cable [Primärkabel]<br />
Backbone Cabling<br />
Main Distributor (MD)<br />
[Hauptverteilter (HV)]<br />
Building Distributor (BD)<br />
[Gebäudeverteiler (GV) ]<br />
MC (Main Cross Connect)<br />
MDA (Main Distribution Area)<br />
Main Distributor Cable<br />
[Hauptverteilerkabel]<br />
Secondary Cable [Sekundärkabel ] Backbone Cabling<br />
Zone Distributor (ZD)<br />
[Bereichsverteiler (BV)]<br />
Floor Distributor (FD) [Etagenverteiler<br />
(EV)]<br />
HC (Horizontal Cross Connect)<br />
HDA (Horizontal Distribution Area)<br />
Zone Distributor Cable<br />
Tertiary/Horizontal Cable [Tertiär-<br />
[Bereichsverteilungskabel] /Horizontalkabel]<br />
Horizontal Cabling<br />
Local Distribution Point (LDP)<br />
[Lokaler Verteilpunkt (LVP)]<br />
Consolidation Point (CP) [Sammelpunkt<br />
(SP)]<br />
CP* (Consolidation Point)<br />
ZDA (Zone Distribution Area)<br />
Local Distribution Point Cable Consolidation Point Cable<br />
[Lokales Verteilpunktkabel] [Sammelpunktkabel]<br />
Horizontal Cabling<br />
Equipment Outlet (EO)<br />
[Geräteanschluss (GA)]<br />
Telecommunications Outlet (TO)]<br />
[Informationstechnischer Anschluss (TA)<br />
EO (Equipment Outlet)<br />
EDA (Equipment Distribution Area)<br />
Unique assignment exists of functional elements to rooms, though in the TIA-942 it is data center areas rather<br />
than the functional elements that are at the forefront. Given a detailed examination, we see that this topology is<br />
the same for ISO/IEC 24764 and EN 50173-5.<br />