16.01.2015 Views

R&M Data Center Handbook

R&M Data Center Handbook

R&M Data Center Handbook

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

www.datacenter.rdm.com<br />

Higher temperatures may be selected today than were previously, thanks to the improved manufacturer quality of<br />

silicon chips. Preset temperatures of 24° C to 27° C and relative humidities of about 60% are currently state of the<br />

art.<br />

In the closed-circuit air conditioning principle, the air cooled by the air conditioning system circulates to IT<br />

components, takes in heat and the warmed air then reaches the air conditioning system again in the form of return<br />

air that is to be re-cooled. Only a small amount of outside air is introduced into the room that is to be airconditioned<br />

and used for air exchange. Optimal conditions with respect to temperature and relative humidity can<br />

only be achieved with closed-circuit air-conditioning units, or so-called precision air-conditioning units. The energy<br />

used in these systems is better utilized, i.e. reducing the temperature of return air is the first priority.<br />

These units are contrasted with comfort air-conditioning units used for residential and office spaces, such as split<br />

air-conditioning units, which continuously use a large portion of the energy they consume to dehumidify recirculated<br />

air. This can lead not only to critical room conditions but also to significantly higher operating costs, which is why<br />

their use is not economically feasible in data centers.<br />

Rack arrangement and air flow are both crucial factors in the performance of closed-circuit air conditioning systems.<br />

This is why 19’’ cabinets, in particular, are currently arranged in accordance with the so-called hot aisle/cold aisle<br />

principle, so as to reproduce, as best as possible, the horizontal air flow required for IT and network components.<br />

In this arrangement, the air flow is forced to take in the heat from the active components on its path from the<br />

raised floor back to the air-conditioning. This process differentiates between self-contained duct systems (Plenum<br />

Feed, Plenum Return) and via room air (Room Feed, Room Return).<br />

One must make sure that the 19” cabinets<br />

correspond to the circulation principle that is<br />

selected. In “Room Feed, Room Return”,<br />

cabinet doors (if they exist) must be perforated<br />

at least 60% in order to permit air<br />

circulation. The floor of the cabinet should be<br />

sealed to the raised floor at least on the<br />

warm side, in order to avoid mixing air<br />

currents. A cooling principle of this type is<br />

suited for power up to approximately 10 kW<br />

per cabinet.<br />

Plenum Feed, Plenum Return (Source: Conteg)<br />

In “Plenum Feed, Plenum Return”, it is absolutely<br />

necessary that the cabinet has doors<br />

and that they can be sealed airtight. By<br />

contrast, the floor must be sealed on the<br />

warm side and be open on the cold side.<br />

These solutions are suitable for power of<br />

approximately 15 kW.<br />

Within the cabinet no openings may exist between the cold side and the warm side, to ensure that mixtures and<br />

microcirculations are avoided. Unused height units and feedthroughs should be closed with blind panels and seals.<br />

Performance can be further optimized by containment of the cold or warm aisle (Contained Cold/Warm Aisle).<br />

Of crucial importance is the height of the raised floor, over which the area of the data center is to be provided with<br />

cold air. Supply air comes out via slot plates or grids in the cold aisle. After it is warmed by the IT devices, the<br />

return air reaches the air conditioning system again to be re-cooled.<br />

Direct-Cooling Principle – Water-Cooled Server Rack<br />

Direct cooling of racks must be implemented when heat loads exceed 10 to 15 kW<br />

per cabinet. This is realized via a heat exchanger installed in the immediate vicinity<br />

of the servers. These are usually heat exchangers cooled with cold water, that are<br />

arranged either below or next to the 19” fixtures. Up to 40 kW of heat per rack can<br />

be drawn off in this way. A cold-water infrastructure must be provided in the rack<br />

area for this method.<br />

The water-cooled racks ensure the proper climatic conditions for their server cabinets,<br />

and are therefore self-sufficient with respect to the room air-conditioning system. In<br />

buildings with a low distance between floors, water-cooled server racks are a good<br />

option for drawing off high heat loads safely without having to use a raised floor. The<br />

high-performance cooling system required for higher power also includes a cold and<br />

hot aisle containment.<br />

Page 70 of 156 © 08/2011 Reichle & De-Massari AG R&M <strong>Data</strong> <strong>Center</strong> <strong>Handbook</strong> V2.0

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!