Control <strong>Products</strong><br />

Oscilloscopes Digital Power<br />

Analyzer<br />

Data Acquisition<br />

Equipment<br />

Optical<br />

Measuring<br />

Instruments<br />

Generators,<br />

Sources<br />

Next Generation,<br />

Datacomm<br />

Measuring<br />

Instruments<br />

GREEN Series Digital Indicating<br />

Controller with Industrial Ethernet<br />

Simple, High-performance Type<br />

UT351- * A<br />

Digital Indicating Controller with<br />

Industrial Ethernet 1, 2<br />

• Easy-to-operate general-purpose<br />

controllers<br />

• Large clear PV display (with Active Color<br />

PV Display)<br />

• A/M mode switching key (standard)<br />

• Heating/cooling control included<br />

• Retransmission output (standard)<br />

(also us able as the power supply for the<br />

sen sor)<br />

• Number of combination of setpoints and<br />

PID parameters: 4<br />

1: Ethernet is the trademark of XEROX Corporation.<br />

2: Please prepare Ethernet cable individually.<br />

UT351- *A/UT551- *A to *D<br />

UT351- * A Specifi cations<br />

• Input accuracy:<br />

±0.1%, control cycle 250 ms<br />

• Dimension:<br />

96 (W) × 96 (H) × 100 (D) mm<br />

• Universal input: TC, DCV, RTD<br />

• Universal output:<br />

voltage pulse, 4 to 20 mA, and relay<br />

•Overshoot suppression “super” function,<br />

hunting suppression “super2” function and<br />

auto-tuning (standard)<br />

• Alarm output: 3 points (standard)<br />

• Heater burnout alarm specifi able<br />

• Ethernet communication function<br />

10BASE-T/100BASE-TX<br />

Modbus/TCP protocol<br />

• Gate way communication function<br />

• High reliability:<br />

conforms to UL, CSA, and CE-mark<br />

certifi cation<br />

Front panel con forms to IP55 or<br />

equivalent (dust- and drip-proof)<br />

• Security function using password<br />

•Weight: Approx. 0.7 kg<br />

•Parameter settings on a PC is available<br />

with the LL100 parameters setting tool.<br />

Broad-ranging, High-performance Type<br />

UT551- * A to * D<br />

Digital Indicating Controller with<br />

Industrial Ethernet 1, 2<br />

• High performance controllers with lots of<br />

functions<br />

• Large clear PV display (with Active Color<br />

PV Display)<br />

• Position proportional control in clud ed<br />

• Remote setpoint input available<br />

• Retransmission output (standard)<br />

(also us able as the power supply for the<br />

sen sor)<br />

• Number of setpoint and PID parameter<br />

com bi na tions: up to 8<br />

• Easily applied to cascade control or input<br />

switching control by selecting function<br />

modes<br />

1: Ethernet is the trademark of XEROX Corporation.<br />

2: Please prepare Ethernet cable individually.<br />

http://www.yokogawa.com/ns/cis/utup/ut/ns-index_ut.htm<br />

UT551 Specifi cations<br />

• Input accuracy:<br />

±0.1%, control cycle 100 ms/200 ms/500 ms<br />

• Dimension:<br />

96 (W) × 96 (H) × 100 (D) mm<br />

• Universal input: TC, DCV, RTD<br />

• Universal output:<br />

voltage pulse, 4 to 20 mA, and relay<br />

•Overshoot suppression “super” function,<br />

hunting suppression “super2” function and<br />

auto-tuning (standard)<br />

• Extended DI/O (alarm output up to 8<br />

points available)<br />

• Ethernet communication function<br />

10BASE-T/100BASE-TX<br />

Modbus/TCP protocol<br />

• Gate way communication function<br />

• High reliability:<br />

conforms to UL, CSA, and CE-mark<br />

certifi cation<br />

Front panel con forms to IP55 or<br />

equivalent (dust- and drip-proof)<br />

• Security function using password<br />

•Parameter settings on a PC is available<br />

with the LL100 parameters setting tool<br />

•Weight: Approx. 1 kg or less<br />

Wireless<br />

Communication<br />

Test Instruments<br />

Other Test &<br />

Measurement<br />

Instruments<br />

PC-Based Parameters<br />

Setting Tools<br />

LL100/LL200, LL1100/LL1200 (for US1000)<br />

http://www.yokogawa.com/ns/cis/utup/ll/ns-index_ll.htm<br />

Optical communication adapter<br />

LL100/LL1100 Parameters Setting Tool<br />

Recorders Control <strong>Products</strong> Data Acquisition<br />

Software Suite<br />

Portable Test<br />

Instruments<br />

Controllers<br />

USB cable<br />

LL100/LL200, LL1100/LL1200 (for US1000)<br />

Light Loader<br />

LL100/LL1100 and LL200/LL1200 are software package<br />

that en ables you to set the controllers confi guration<br />

parameters.<br />

The optical communication adapter will connect and<br />

communicate through the drip- and dust-proof panel of the<br />

con trol ler.<br />

It can easily be set via Ethernet. (for UT351-*A, UT551)<br />

PC<br />

• Applicable Controllers: UT320, UT321, UT350,UT351,<br />

UT420, UT450, UT520, UT550,<br />

UT551, UT750, US1000, UP350,<br />

UP351, UP550, UP750<br />

The LL100/LL1100 *1 PC-based Parameters Setting Tool is<br />

a software package used to set the setup parameters,<br />

operating parameters, and program patterns *2 of the<br />

GREEN Se ries controllers from a personal computer. This<br />

tool allows users to download, upload, print out parameters,<br />

and dis play PV trend data during PID tuning etc.<br />

*1: The LL1100 is for US1000 controller only.<br />

*2: For program controllers only.<br />

LL200/LL1200 Custom Computation Building Tool<br />

• Applicable Controllers: US1000, UT750, UP750<br />

The LL200/LL1200 *1 PC-based Custom Computation<br />

Building Tool is a soft ware pack age used to create custom<br />

com pu ta tion and custom display func tions. This tool also<br />

cov ers the functions of the LL100/LL1100 PC-based<br />

Parameters Setting Tool. The custom computation build ing<br />

function, the main function of this pack age, en ables users to<br />

formulate computations graph i cal ly. This tool has an online<br />

help function that provides explanations of the com pu ta tion<br />

modules.<br />

*1: The LL1200 is for US1000 controller only.<br />

Tuning screen<br />

Program pattern setting up screen<br />

Meters <strong>Products</strong><br />

62<br />

Multi-monitor display