Protection<br />

Setting ranges<br />

Functions Settings Time delays<br />

ANSI 67N/67NC type 1 - Directional earth fault, according to I0 projection<br />

Characteristic angle -45°, 0°, 15°, 30°, 45°, 60°, 90°<br />

Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s<br />

Vs0 set point<br />

2 to 80% of Unp<br />

Memory time T0mem time 0; 0.05 s to 300 s<br />

V0mem validity set point 0; 2 to 80% of Unp<br />

ANSI 67N/67NC type 2 - Directional earth fault, according to I0 magnitude with half-plane tripping zone<br />

Characteristic angle -45°, 0°, 15°, 30°, 45°, 60°, 90°<br />

Tripping curve Tripping time delay Reset time<br />

Definite time<br />

DT<br />

SIT, LTI, VIT, EIT, UIT (1) DT<br />

RI<br />

DT<br />

IEC, SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT<br />

IEEE: MI (D), VI (E), EI (F) DT or IDMT<br />

IAC: I, VI, EI<br />

DT or IDMT<br />

Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s<br />

0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0<br />

Vs0 set point<br />

2 to 80% of Unp<br />

Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s<br />

IDMT (IDMT; reset time)<br />

0.5 s to <strong>20</strong> s<br />

ANSI 67N/67NC type 3 - Directional earth fault, according to I0 magnitude with angular sector tripping zone<br />

Angle at start of tripping zone 0° to 359°<br />

Angle at end of tripping zone 0° to 359°<br />

Is0 set point CSH core balance CT (2 A rating) 0.2 A to 30 A Definite time Inst.; 0.05 to 300 s<br />

1 A CT + CSH30<br />

0.1 to 15 In0 (min. 0.1 A)<br />

(sensitive, In0 = 0.1 CT In)<br />

Core balance CT + ACE990 (range 1) 0.1 to In0 (min. 0.1 A)<br />

Vs0 set point Calculated V0 (sum of 3 2 to 80 % of Unp<br />

voltages)<br />

Measured V0 (external VT) 0.6 to 80 % of Unp<br />

ANSI 81H - Overfrequency<br />

<strong>series</strong> <strong>20</strong> 50 to 53 Hz or 60 to 63 Hz 0.1 s to 300 s<br />

<strong>series</strong> <strong>40</strong> 50 to 55 Hz or 60 to 65 Hz 0.1 s to 300 s<br />

ANSI 81L - Underfrequency<br />

<strong>series</strong> <strong>20</strong> 45 to 50 Hz or 55 to 60 Hz 0.1 s to 300 s<br />

<strong>series</strong> <strong>40</strong> <strong>40</strong> to 50 Hz or 50 to 60 Hz 0.1 s to 300 s<br />

ANSI 81R - Rate of change of frequency<br />

0.1 to 10 Hz/s Inst.; 0.15 s to 300 s<br />

(1) Tripping as of 1.2 Is.<br />