Connection diagrams<br />
Residual current input<br />
MT10991<br />
Variant 1: residual current calculation by sum of 3 phase currents<br />
The residual current is obtained by taking the vector sum of the 3 phase currents I1,<br />
I2 and I3, measured by three 1 A or 5 A CTs or by three LPCT type sensors.<br />
See current input connection diagrams.<br />
Variant 2: residual current measurement by CSH1<strong>20</strong> or CSH<strong>20</strong>0 core balance CT (standard connection)<br />
Arrangement recommended for the protection of isolated or compensated neutral<br />
systems in which very low fault currents need to be detected.<br />
Setting range from 0.1 In0 to 15 In0, with In0 = 2 A or <strong>20</strong> A (or 5 A for <strong>series</strong> <strong>40</strong>)<br />
according to parameter setting.<br />
MT11045<br />
Variant 3: residual current measurement by 1 A or 5 A CT and CSH30 interposing ring CT<br />
The CSH30 interposing ring CT is used to connect <strong>Sepam</strong> to 1 A or 5 A CTs to<br />
measure the residual current.<br />
b connection of CSH30 interposing ring CT to 1 A CT: make 2 turns through the CSH<br />
primary winding<br />
b connection of CSH30 interposing ring CT to 5 A CT: make 4 turns through the CSH<br />
primary winding<br />
b with <strong>series</strong> <strong>40</strong>, the sensitivity can be multiplied by 10<br />
by parameter setting of In0 = In/10.<br />
Setting range from 0.1 In to 15 In, or 0.01 In to 1.5 In (<strong>series</strong> <strong>40</strong>)<br />
with In = CT primary current.<br />
DE50589<br />
MT11046<br />
Variant 4: residual current measurement by core balance CT with ratio 1/n (n between 50 and 1500)<br />
The ACE990 is used as an interface between a MV core balance CT with ratio 1/n<br />
(50 < n < 1500) and the <strong>Sepam</strong> residual current input.<br />
This arrangement makes it possible to keep the existing core balance CTs in the<br />
installation.<br />
Setting range from 0.1 In0 to 15 In0, with In0 = k.n,<br />
with n = number of turns through core balance CT<br />
and k = factor to be determined according to the wiring of the ACE990 and the<br />
parameter setting used by <strong>Sepam</strong>, among <strong>20</strong> discrete values from 0.00578 to<br />
0.26316.<br />