Connection diagrams <strong>Sepam</strong> <strong>series</strong> <strong>40</strong><br />
S<strong>40</strong> / S41 / S42 types<br />
T<strong>40</strong> / T42 / M41 / G<strong>40</strong> types<br />
B<br />
Ring lug<br />
4mm<br />
CCA630 1.5 to 6 mm 2<br />
(AWG 16 to AWG 10)<br />
C RJ45 CCA612<br />
D RJ45 CCA770: L = 0.6 m<br />
CCA772: L= 2m<br />
CCA774: L=4m<br />
E<br />
Connection to 1 A / 5 A current sensors<br />
Connector Type Ref. Cable<br />
A<br />
Screwtype<br />
CCA6<strong>20</strong> 1 wire 0.2 to 2.5 mm 2<br />
(u AWG 24-12)<br />
2 wires 0.2 to 1 mm 2<br />
(u AWG 24-16)<br />
Ring lug<br />
6.35 mm<br />
CCA622<br />
Screwtype<br />
Ring lug<br />
6.35 mm<br />
CCA626 1 wire 0.2 to 2.5 mm 2<br />
(u AWG 24-12)<br />
2 wires 0.2 to 1 mm 2<br />
(u AWG 24-16)<br />
CCA627<br />
DE50596<br />
(1) This type of connection allows the calculation of residual voltage.<br />
(2) Accessory for bridging terminals 3 and 5 supplied with CCA626 connector.<br />
19