Control and monitoring<br />
Logic inputs and outputs<br />
MT10680<br />
MT10681<br />
4 output relays on the base unit<br />
The 4 relay outputs O1, O2, O3 and O4 on the base unit are connected to<br />
connector A .<br />
Connector A of the base unit may be either of the following:<br />
b CCA6<strong>20</strong> screw-type connector<br />
b CCA622 ring lug connector.<br />
O1 and O2 are 2 control outputs used by the breaking device control function for:<br />
b O1: breaking device tripping<br />
b O2: inhibition of breaking device closing.<br />
O3 and O4 are indication outputs, only O4 can be activated by the watchdog function.<br />
CCA6<strong>20</strong> connector<br />
(screw-type terminal block for<br />
straight fittings).<br />
CCA622 connector<br />
(terminal block for ring lugs)<br />
MT10683<br />
MES114 module (10 inputs / 4 outputs).<br />
Optional input/output modules<br />
The 4 outputs on the base unit may be completed by adding an MES114 10 input/<br />
4 output module on the back of the base unit.<br />
3 modules are offered, MES114, MES114E or MES114F, to suit the different input<br />
voltage supply ranges.<br />
The modules offer different switching thresholds as well.<br />
The MES114 module is fully compatible with the MES108 (4 input/4 output) module<br />
which is no longer commercialized.<br />
Input characteristics<br />
b 10 potential-free inputs<br />
b external power source.<br />
Logic inputs MES114 MES114E MES114F<br />
Voltage 24<br />
to 250 V DC<br />
Range 19.2<br />
to 275 V DC<br />
110<br />
to 125 V DC<br />
88<br />
to 150 V DC<br />
110 V AC 2<strong>20</strong><br />
to 250 V DC<br />
88<br />
to 132 V AC<br />
176<br />
to 275 V DC<br />
2<strong>20</strong><br />
to 2<strong>40</strong> V AC<br />
176<br />
to 264 V AC<br />
Frequency - - 47 to 63 Hz - 47 to 63 Hz<br />
Typical consumption 3 mA 3 mA 3 mA 3 mA 3 mA<br />
Typical switching<br />
threshold<br />
14 V DC 82 V DC 58 V AC 154 V DC 1<strong>20</strong> V AC<br />
Input limit At state 1 u 19 V DC u 88 V DC u 88 V AC u 176 V DC u 176 V AC<br />
voltage<br />
At state 0 y 6 V DC y 75 V DC y 22 V AC y 137 V DC y 48 V AC<br />
Output characteristics<br />
b 4 relay outputs O11, O12, O13, O14<br />
v O11: control output, used for breaking device closing<br />
v O12, O13, O14: indication outputs.<br />
Connection to screw-type connectors<br />
b 1 wire with cross-section 0.2 to 2.5 mm² (u AWG 24-12)<br />
b or 2 wires with cross-section 0.2 to 1 mm² (u AWG 24-16).<br />
MT10684<br />
O1<br />
A<br />
5<br />
4<br />
D<br />
+<br />
MT10685<br />
O1<br />
A<br />
5<br />
4<br />
D<br />
+<br />
Wiring of the breaking device trip circuit<br />
Wiring to be used when the "CB control" function is activated.<br />
I11<br />
I12<br />
M<br />
1<br />
2<br />
4<br />
5<br />
I11<br />
I12<br />
M<br />
1<br />
2<br />
4<br />
5<br />
Wiring for shunt trip coil.<br />
With monitoring of trip circuit<br />
and open/closed matching.<br />
Wiring for undervoltage trip<br />
unit.<br />
With monitoring of open /<br />
closed matching.<br />