Control and monitoring<br />

Logic inputs and outputs<br />

MT10680<br />

MT10681<br />

4 output relays on the base unit<br />

The 4 relay outputs O1, O2, O3 and O4 on the base unit are connected to<br />

connector A .<br />

Connector A of the base unit may be either of the following:<br />

b CCA6<strong>20</strong> screw-type connector<br />

b CCA622 ring lug connector.<br />

O1 and O2 are 2 control outputs used by the breaking device control function for:<br />

b O1: breaking device tripping<br />

b O2: inhibition of breaking device closing.<br />

O3 and O4 are indication outputs, only O4 can be activated by the watchdog function.<br />

CCA6<strong>20</strong> connector<br />

(screw-type terminal block for<br />

straight fittings).<br />

CCA622 connector<br />

(terminal block for ring lugs)<br />

MT10683<br />

MES114 module (10 inputs / 4 outputs).<br />

Optional input/output modules<br />

The 4 outputs on the base unit may be completed by adding an MES114 10 input/<br />

4 output module on the back of the base unit.<br />

3 modules are offered, MES114, MES114E or MES114F, to suit the different input<br />

voltage supply ranges.<br />

The modules offer different switching thresholds as well.<br />

The MES114 module is fully compatible with the MES108 (4 input/4 output) module<br />

which is no longer commercialized.<br />

Input characteristics<br />

b 10 potential-free inputs<br />

b external power source.<br />

Logic inputs MES114 MES114E MES114F<br />

Voltage 24<br />

to 250 V DC<br />

Range 19.2<br />

to 275 V DC<br />

110<br />

to 125 V DC<br />

88<br />

to 150 V DC<br />

110 V AC 2<strong>20</strong><br />

to 250 V DC<br />

88<br />

to 132 V AC<br />

176<br />

to 275 V DC<br />

2<strong>20</strong><br />

to 2<strong>40</strong> V AC<br />

176<br />

to 264 V AC<br />

Frequency - - 47 to 63 Hz - 47 to 63 Hz<br />

Typical consumption 3 mA 3 mA 3 mA 3 mA 3 mA<br />

Typical switching<br />

threshold<br />

14 V DC 82 V DC 58 V AC 154 V DC 1<strong>20</strong> V AC<br />

Input limit At state 1 u 19 V DC u 88 V DC u 88 V AC u 176 V DC u 176 V AC<br />

voltage<br />

At state 0 y 6 V DC y 75 V DC y 22 V AC y 137 V DC y 48 V AC<br />

Output characteristics<br />

b 4 relay outputs O11, O12, O13, O14<br />

v O11: control output, used for breaking device closing<br />

v O12, O13, O14: indication outputs.<br />

Connection to screw-type connectors<br />

b 1 wire with cross-section 0.2 to 2.5 mm² (u AWG 24-12)<br />

b or 2 wires with cross-section 0.2 to 1 mm² (u AWG 24-16).<br />

MT10684<br />

O1<br />

A<br />

5<br />

4<br />

D<br />

+<br />

MT10685<br />

O1<br />

A<br />

5<br />

4<br />

D<br />

+<br />

Wiring of the breaking device trip circuit<br />

Wiring to be used when the "CB control" function is activated.<br />

I11<br />

I12<br />

M<br />

1<br />

2<br />

4<br />

5<br />

I11<br />

I12<br />

M<br />

1<br />

2<br />

4<br />

5<br />

Wiring for shunt trip coil.<br />

With monitoring of trip circuit<br />

and open/closed matching.<br />

Wiring for undervoltage trip<br />

unit.<br />

With monitoring of open /<br />

closed matching.<br />

25