Connection diagrams<br />

<strong>Sepam</strong> <strong>series</strong> <strong>40</strong> voltage inputs<br />

DE51050<br />

The phase and residual voltage transformer secondary circuits are connected<br />

directly to the connector marked E .<br />

The 3 impedance matching and isolation transformers are integrated in the<br />

<strong>Sepam</strong> <strong>series</strong> <strong>40</strong> base unit.<br />

Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)<br />

Phase voltage sensor parameter setting<br />

Residual voltage sensor parameter setting<br />

Voltages measured<br />

Values calculated<br />

3V<br />

3V sum<br />

V1, V2, V3<br />

U21, U32, U13, V0, Vd, Vi, f<br />

Measurements unavailable<br />

Protection functions unavailable<br />

(according to type of <strong>Sepam</strong>)<br />

None<br />

None<br />

DE51006<br />

Variant 2: measurement of 2 phase-to-phase voltages and residual voltage<br />

Phase voltage sensor parameter setting<br />

Residual voltage sensor parameter setting<br />

Voltages measured<br />

Values calculated<br />

Measurements unavailable<br />

Protection functions unavailable<br />

(according to type of <strong>Sepam</strong>)<br />

U21, U32<br />

External VT<br />

U21, U32, V0<br />

U13, V1, V2, V3, Vd, Vi, f<br />

None<br />

None<br />

MT10994<br />

Variant 3: measurement of 2 phase-to-phase voltages<br />

Phase voltage sensor parameter setting<br />

Residual voltage sensor parameter setting<br />

Voltages measured<br />

Values calculated<br />

Measurements unavailable<br />

Protection functions unavailable<br />

(according to type of <strong>Sepam</strong>)<br />

U21, U32<br />

None<br />

U21, U32<br />

U13, Vd, Vi, f<br />

V1, V2, V3, V0<br />

67N/67NC, 59N<br />

MT11011<br />

Variant 4: measurement of 1 phase-to-phase voltage and residual voltage<br />

Phase voltage sensor parameter setting<br />

Residual voltage sensor parameter setting<br />

Voltages measured<br />

Values calculated<br />

Measurements unavailable<br />

Protection functions unavailable<br />

(according to type of <strong>Sepam</strong>)<br />

U21<br />

External VT<br />

U21, V0<br />

f<br />

U32, U13, V1, V2, V3, Vd, Vi<br />

67, 47, 27D, 32P, 32Q/<strong>40</strong>, 27S<br />

MT11016<br />

Variant 5: measurement of 1 phase-to-phase voltage<br />

Phase voltage sensor parameter setting<br />

Residual voltage sensor parameter setting<br />

Voltages measured<br />

Values calculated<br />

Measurements unavailable<br />

Protection functions unavailable<br />

(according to type of <strong>Sepam</strong>)<br />

U21<br />

None<br />

U21<br />

f<br />

U32, U13, V1, V2, V3, V0, Vd, Vi<br />

67, 47, 27D, 32P, 32Q/<strong>40</strong>,<br />