Sepam series 20 Sepam series 40 - POWERLAB
Sepam series 20 Sepam series 40 - POWERLAB
Sepam series 20 Sepam series 40 - POWERLAB
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Connection diagrams<br />
<strong>Sepam</strong> <strong>series</strong> <strong>40</strong> voltage inputs<br />
DE51050<br />
The phase and residual voltage transformer secondary circuits are connected<br />
directly to the connector marked E .<br />
The 3 impedance matching and isolation transformers are integrated in the<br />
<strong>Sepam</strong> <strong>series</strong> <strong>40</strong> base unit.<br />
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)<br />
Phase voltage sensor parameter setting<br />
Residual voltage sensor parameter setting<br />
Voltages measured<br />
Values calculated<br />
3V<br />
3V sum<br />
V1, V2, V3<br />
U21, U32, U13, V0, Vd, Vi, f<br />
Measurements unavailable<br />
Protection functions unavailable<br />
(according to type of <strong>Sepam</strong>)<br />
None<br />
None<br />
DE51006<br />
Variant 2: measurement of 2 phase-to-phase voltages and residual voltage<br />
Phase voltage sensor parameter setting<br />
Residual voltage sensor parameter setting<br />
Voltages measured<br />
Values calculated<br />
Measurements unavailable<br />
Protection functions unavailable<br />
(according to type of <strong>Sepam</strong>)<br />
U21, U32<br />
External VT<br />
U21, U32, V0<br />
U13, V1, V2, V3, Vd, Vi, f<br />
None<br />
None<br />
MT10994<br />
Variant 3: measurement of 2 phase-to-phase voltages<br />
Phase voltage sensor parameter setting<br />
Residual voltage sensor parameter setting<br />
Voltages measured<br />
Values calculated<br />
Measurements unavailable<br />
Protection functions unavailable<br />
(according to type of <strong>Sepam</strong>)<br />
U21, U32<br />
None<br />
U21, U32<br />
U13, Vd, Vi, f<br />
V1, V2, V3, V0<br />
67N/67NC, 59N<br />
MT11011<br />
Variant 4: measurement of 1 phase-to-phase voltage and residual voltage<br />
Phase voltage sensor parameter setting<br />
Residual voltage sensor parameter setting<br />
Voltages measured<br />
Values calculated<br />
Measurements unavailable<br />
Protection functions unavailable<br />
(according to type of <strong>Sepam</strong>)<br />
U21<br />
External VT<br />
U21, V0<br />
f<br />
U32, U13, V1, V2, V3, Vd, Vi<br />
67, 47, 27D, 32P, 32Q/<strong>40</strong>, 27S<br />
MT11016<br />
Variant 5: measurement of 1 phase-to-phase voltage<br />
Phase voltage sensor parameter setting<br />
Residual voltage sensor parameter setting<br />
Voltages measured<br />
Values calculated<br />
Measurements unavailable<br />
Protection functions unavailable<br />
(according to type of <strong>Sepam</strong>)<br />
U21<br />
None<br />
U21<br />
f<br />
U32, U13, V1, V2, V3, V0, Vd, Vi<br />
67, 47, 27D, 32P, 32Q/<strong>40</strong>,<br />
67N/67NC, 59N, 27S<br />
23