Control and monitoring<br />

Logic input / output assignment<br />

for <strong>Sepam</strong> <strong>series</strong> <strong>40</strong><br />

Chart of logic input and output assignments<br />

for <strong>Sepam</strong> <strong>series</strong> <strong>40</strong> applications<br />

The functions defined in the chart below are associated with a logic input by<br />

configuration. This means that the functions used may be adapted to suit needs<br />

within the limits of the logic inputs available. They may be reversed for undervoltage<br />

type operation.<br />

Functions S<strong>40</strong>, S41 S42 T<strong>40</strong>, T42 M41 G<strong>40</strong> Assignment<br />

Logic inputs<br />

Open position b b b b b I11<br />

Closed position b b b b b I12<br />

Logic discrimination, receive blocking input 1 b b b b Free<br />

Logic discrimination, receive blocking input 2 b Free<br />

Switching of groups of settings A/B b b b b b I13<br />

External reset b b b b b Free<br />

External tripping 1 b b b b b Free<br />

External tripping 2 b b b b b Free<br />

External tripping 3 b b b b b Free<br />

Buchholz/gas tripping b Free<br />

Thermostat tripping b Free<br />

Pressure tripping b Free<br />

Thermistor tripping b b b Free<br />

Buchholz/gas alarm b Free<br />

Thermostat alarm b Free<br />

Pressure alarm b Free<br />

Thermistor alarm b b b Free<br />

End of charging position b b b b b Free<br />

Inhibit remote control b b b b b Free<br />

SF6 b b b b b Free<br />

Inhibit recloser b b Free<br />

External synchronization b b b b b I21<br />

Inhibit thermal overload b b b Free<br />

Switching of thermal settings b b b Free<br />

Motor re-acceleration b Free<br />

Rotor rotation detection b Free<br />

Inhibit undercurrent b Free<br />

Inhibit closing b b b b b Free<br />

Open order b b b b b Free<br />

Close order b b b b b Free<br />

Phase voltage transformer fuse melting b b b b b Free<br />

Residual voltage transformer fuse melting b b b b b Free<br />

External positive active energy counter b b b b b Free<br />

External negative active energy counter b b b b b Free<br />

External positive reactive energy counter b b b b b Free<br />

External negative reactive energy counter b b b b b Free<br />

Logic outputs<br />

Tripping b b b b b O1<br />

Inhibit closing b b b b b O2<br />

Watchdog b b b b b O4<br />

Close order b b b b b O11<br />

NB: all of the logic inputs are available via the communication link and are accessible in the SFT2841 matrix for other non predefined applications.<br />