Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
4Adding a <strong>DeviceNet</strong> Slave Module to the PLC ConfigurationFirst, add the <strong>Series</strong> <strong>90</strong>-<strong>30</strong> <strong>DeviceNet</strong> Slave Module (IC693DNS201) to the PLC rackconfiguration. The IC693DNS201 is compatible with any <strong>Series</strong> <strong>90</strong>-<strong>30</strong> CPU except IC693CPU321and IC693CPU340. It requires release 8.0 CPU firmware as a minimum. Release 10.6 or later isrecommended, if available for your particular CPU.1. In that configuration, in the Project tab of the Navigator, expand the Hardware Configurationfolder.2. In the Hardware Configuration folder, right click the PLC Slot for the <strong>DeviceNet</strong> SlaveModule. It can be any slot except slot 1 of a modular CPU rack.3. Select Add Module from the shortcut menu.HardwareConfiguration FolderNavigator WindowShort Cut Menu4. The Module Catalog dialog box appears. To add a <strong>DeviceNet</strong> Slave Module, click on theCommunications tab. Select the IC693DNS201 <strong>DeviceNet</strong> Slave from the list and click OK.<strong>GFK</strong>-<strong>2196</strong> Chapter 4 PLC Configuration for the <strong>DeviceNet</strong> Slave 4-3