2.2.6 4AO Analog Output Board<br />

The 4AO Analog Output Board (P/N 815-3030) (Figure<br />

2-13) is configured with four analog output connections<br />

that provide a variable voltage signal to any of four<br />

analog devices that may be controlled by a single <strong>E2</strong>. Two<br />

4-20mA outputs are provided for channels 1 and 2. The<br />

4-20mA outputs provide a variable current for applications<br />

that are either externally powered or that require power<br />

from the 4AO board.<br />

5<br />

4<br />

7 8<br />

Transmitting (TX ) and Receiving (RX) LEDs<br />

Hand-held Terminal (HHT) Jack<br />

Figure 2-13 - 4AO Analog Output Board (P/N 815-3030)<br />

The previous generation 4AO Analog Output Board,<br />

(P/N 810-3030) (Figure 2-14) is configured with four analog<br />

output connections that provide a variable voltage signal<br />

to any of four analog devices that may be controlled by<br />

a single <strong>E2</strong>.<br />

Figure 2-14 - 4AO Analog Output Board - DISCONTINUED<br />

8<br />

9<br />

Alarm and Status Indicator LEDs<br />

Analog Outputs (4)<br />

4-20mA Channels (2)<br />

DISCONTINUED<br />

9<br />

2.2.7 8DO Digital Output Board<br />

and PMAC II Anti-Sweat Controller<br />

For control of anti-sweat heaters, Retail Solutions supplies<br />

the 8DO Digital Output board (P/N 810-3050). The<br />

8DO has eight outputs which may pulse up to 150mA at<br />

12VDC.<br />

Since the 8DO is primarily designed to control antisweat<br />

heaters, the 8DO is the heart of Retail Solutions’<br />

Pulse Modulated Anti-Sweat Control (PMAC II) panel.<br />

The PMAC II (P/N 851-1000) provides 16 channels of<br />

anti-sweat control circuitry. The PMAC II panel combines<br />

the 8DO with high-capacity relays in a single enclosure,<br />

providing 256 total amps of anti-sweat heater operation.<br />

The 8DO is shown in Figure 2-15. The PMAC II is<br />

shown in Figure 2-16.<br />

Figure 2-15 - 8DO Digital Output Board<br />

Figure 2-16 - PMAC II Anti-Sweat Control Panel<br />

2-10 • <strong>E2</strong> RX/BX/CX I&O <strong>Manual</strong> 026-1610 Rev 10 06-APR-2010