Setting Up the <strong>LUTM</strong> <strong>Controller</strong>LUC•T AdvancedControl UnitFunctions performed by the advanced control unit.• Protection:- against overloads, class 10 (LUCBT1BL) or 20 (LUCDT1BL)- against loss of phase and phase imbalance• Current setting on front panel• Thermal trip test• Reset:- manual- remote or automatic in conjunction with a function module or acommunication module• Display (motor load) with a function module or a communicationmodule• Alarm: with a function module (e.g., LUFW10)Setting the Advanced Control Unit, p. 27LUCMTMultifunctionControl UnitFunctions performed by the multifunction control unit.• Protection• Alarm• DiagnosticsThese three functions can be configured and monitored.• Reset:- manual- remote or automaticRefer to the documentation for this product.LUFW10Function ModuleFunctions performed by the "Alarm on thermal overload" function module.• Determination of the motor thermal state• Alarm signaling for:- improving the performance of the controlled motor- anticipating complete stop due to a thermal overload• Avoiding, by load shedding, interruptions in use due to tripping onoverloads.All the data processed by this module can be accessed on discretecontacts.Note: Can only be used with the advanced control unit.16 1743233 <strong>03</strong>/<strong>2008</strong>