Operation of the <strong>LUTM</strong> controllerContinuity of service.DANGERLOSS OF OVERLOAD PROTECTION AND PROTECTION AGAINST OTHERFAULTS MONITORED.If the controller base is connected in "continuity of service" mode, the motor will notstop in the event of a thermal overload or any other type of fault.Failure to follow these instructions will result in death or serious injury..1 23 41 Channel 12 Channel 23 Any fault4 Control unitfaultThere is no longer a fault contact in series with the contactor coils.The motors will not stop in the event of the control unit tripping or an external fault.The controller simply tells the PLC why it is taking the necessary measures:• Branch circuit• Starting up the fansIf used with a multifunction control unit, continuity of service is detected on detectionof a fault current; all the detected alarms are set to zero and are no longer managed.38 1743233 <strong>03</strong>/<strong>2008</strong>