4.3.2 Accessory detailsSteam distribution pipe 41-../61-../81-.. for indirect room humidificationThe steam distribution pipes 41-../61-../81-.. are selected on the basis of the duct width (for horizontalinstallation) or the duct height (for vertical installation) and the capacity of the steam humidifier.Important! Always select the longest possible steam distribution pipe (optimum humidification distance).LBSteam distribution pipe 1)for Condair OEMSteam distributionpipeDuct width (B)Type 41-.. Type 61-.. Type 81-.. Length in mm (L) 2) in mm41-200 200 210…40041-350 61-350 81-350 3) 350 400…60041-500 61-500 81-500 3) 500 550…75041-650 61-650 81-650 650 700…90041-800 61-800 81-800 800 900…110041-1000 61-1000 81-1000 1000 1100…130041-1200 61-1200 81-1200 1200 1300…160061-1500 81-1500 1500 1600…200061-1800 81-1800 1800 2000…240061-2000 81-2000 2000 2200…260081-2300 2300 2500…290081-2500 2500 2700…31001)Material: CrNi steel3)up to max. 30 kg/h steam capacity2)special length on requestSteam nozzle (for models OEM 1.. and OEM 2.. only)The steam nozzle “W21” can be mounted in the ventilation duct horizontally orvertically. Keep a minimum distance clearance (A) of 200 mm between nozzleopening and the opposite duct wall.16