04.12.2012 Views

Evaluation of Septic Tank and Subsurface Wetland for

Evaluation of Septic Tank and Subsurface Wetland for

Evaluation of Septic Tank and Subsurface Wetland for

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

BOD was determined to be 53% at Pisgah <strong>and</strong> 63% at Retrieve. These are within the<br />

typical BOD removal efficiency range <strong>of</strong> 46 – 68% reported in literature (Seabloom et al.,<br />

1982; Rahman et al., 1999). The Pisgah wetl<strong>and</strong> removed 52% <strong>of</strong> its influent BOD. This<br />

was below the 68.5 – 92.7% removal efficiency reported in literature <strong>for</strong> SSF wetl<strong>and</strong>s<br />

possibly because <strong>of</strong> the low influent concentration (Vymazal, 2002).<br />

Table 5-1 Five-Day Biochemical Oxygen Dem<strong>and</strong> <strong>for</strong> Pisgah <strong>and</strong> Retrieve<br />

Sanitation Systems<br />

________________________________________________________________________<br />

Sample Arithmetic Mean 90% Confidence Sample<br />

( X ) mg/l Interval mg/l Size (n)<br />

Pisgah First <strong>Septic</strong> <strong>Tank</strong> 58 X ± 20<br />

5<br />

Pisgah Wetl<strong>and</strong> Influent 27 X ± 9<br />

4<br />

Pisgah Wetl<strong>and</strong> Effluent 13 X ± 5<br />

3<br />

Retrieve First <strong>Septic</strong> <strong>Tank</strong> 40 X ± 24<br />

6<br />

Retrieve Wetl<strong>and</strong> Influent 15 X ± 10<br />

5<br />

Retrieve Wetl<strong>and</strong> Effluent 20 X ± 7<br />

7<br />

The first two sets <strong>of</strong> water quality samples indicated that the water in the top <strong>of</strong> the first<br />

chamber <strong>of</strong> the septic tanks had BOD ranging from 8 to 69 mg/l which was lower than<br />

expected. Typical BOD <strong>for</strong> raw sewage ranges from 110 – 350 mg/l in the United States<br />

(Tchobanoglous et al., 2003). Influent BOD to the Montego Bay treatment ponds <strong>and</strong> the<br />

oxidation ditches in Ocho Rios ranges from 47 – 555 mg/l (NWC, 2005). Because <strong>of</strong> the<br />

low influent BOD values, the collection point <strong>for</strong> subsequent samples was moved from<br />

the center <strong>of</strong> the first tank to the inlet tee <strong>of</strong> the first tank. Although there were some<br />

fecal particles in subsequent samples, the BOD <strong>of</strong> septic tank influent ranged from 24 to<br />

83 mg/l.<br />

The temperature <strong>for</strong> five-day incubation <strong>of</strong> BOD samples is to remain 20ºC (68ºF) ± 1ºC.<br />

However, the temperature in the NWC incubator from August 17 to November 15 ranged<br />

from 14.0 - 17.5ºC. After repairs the temperature ranged between 18.5 - 20.5ºC from<br />

38