SEL-751A Settings Sheets - CacheFly
SEL-751A Settings Sheets - CacheFly
SEL-751A Settings Sheets - CacheFly
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SET.2<br />
of 66<br />
<strong>SEL</strong>-<strong>751A</strong> <strong>Settings</strong> <strong>Sheets</strong><br />
Group <strong>Settings</strong> (SET Command)<br />
Date________________<br />
MAXP OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50P3P :=<br />
0.10–20.00 A {1 A nom.})<br />
MAXP OC TRIP DLY (0.00–5.00 sec)<br />
50P3D :=<br />
(Hidden if 50P3P := OFF)<br />
MAXP OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50P3P := OFF) 50P3TC :=<br />
MAXP OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50P4P :=<br />
0.10–20.00 A {1 A nom.})<br />
MAXP OC TRIP DLY (0.00–5.00 sec)<br />
50P4D :=<br />
(Hidden if 50P4P := OFF)<br />
MAXP OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50P4P := OFF) 50P4TC :=<br />
Neutral Overcurrent<br />
NEUT OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom},<br />
0.10–20.00 A {1 A nom}, 0.13–12.50 mA {2.5 mA nom},<br />
5.0–1000.0 mA {50 mA nom})<br />
50N1P :=<br />
NEUT OC TRIP DLY (0.00–5.00 sec) (Hidden if 50N1P := OFF) 50N1D :=<br />
NEUT OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50N1P := OFF) 50N1TC :=<br />
NEUT OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom},<br />
0.10–20.00 A {1 A nom}, 0.13–12.50 mA {2.5 mA nom},<br />
5.0–1000.0 mA {50 mA nom})<br />
50N2P :=<br />
NEUT OC TRIP DLY (0.00–5.00 sec) (Hidden if 50N2P := OFF) 50N2D :=<br />
NEUT OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50N2P := OFF) 50N2TC :=<br />
NEUT OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom},<br />
0.10–20.00 A {1 A nom}, 0.13–12.50 mA {2.5 mA nom},<br />
5.0–1000.0 mA {50 mA nom})<br />
50N3P :=<br />
NEUT OC TRIP DLY (0.00–5.00 sec) (Hidden if 50N3P := OFF) 50N3D :=<br />
NEUT OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50N3P := OFF) 50N3TC :=<br />
NEUT OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom},<br />
0.10–20.00 A {1 A nom}, 0.13–12.50 mA {2.5 mA nom},<br />
5.0–1000.0 mA {50 mA nom})<br />
50N4P :=<br />
NEUT OC TRIP DLY (0.00–5.00 sec) (Hidden if 50N4P := OFF) 50N4D :=<br />
NEUT OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50N4P := OFF) 50N4TC :=<br />
Residual Overcurrent<br />
RES OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50G1P :=<br />
0.10–20.00 A {1 A nom.})<br />
RES OC TRIP DLY (0.00–5.00 sec) (Hidden if 50G1P := OFF) 50G1D :=<br />
RES OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50G1P := OFF) 50G1TC :=<br />
RES OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50G2P :=<br />
0.10–20.00 A {1 A nom.})<br />
RES OC TRIP DLY (0.00–5.00 sec) (Hidden if 50G2P := OFF) 50G2D :=<br />
RES OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50G2P := OFF) 50G2TC :=<br />
RES OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.},<br />
0.10–20.00 A {1 A nom.})<br />
50G3P :=<br />
<strong>SEL</strong>-<strong>751A</strong> Relay Instruction Manual Date Code 20090501