Date _______________<br />

<strong>SEL</strong>-<strong>751A</strong> <strong>Settings</strong> <strong>Sheets</strong><br />

Group <strong>Settings</strong> (SET Command)<br />

SET.5<br />

of 66<br />

Negative-Sequence Time Overcurrent<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.}, 0.10–3.20 A 51QP :=<br />

{1 A nom.})<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51QC :=<br />

(Hidden if 51QP := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_}, 0.05–1.00 {if 51QTD :=<br />

51_C := C_}) (Hidden if 51QP := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51QP := OFF) 51QRS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51QCT :=<br />

(Hidden if 51QP := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec) (Hidden if 51QP := OFF) 51QMR :=<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51QP := OFF) 51QTC :=<br />

Neutral Time Overcurrent<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.}, 0.10–3.20 A<br />

{1 A nom.}, 0.13–2.00 mA {2.5 mA nom.}, 5.0–160.0 mA<br />

{50 mA nom.})<br />

51N1P :=<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51N1C :=<br />

(Hidden if 51N1P := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_}, 0.05–1.00 {if 51N1TD :=<br />

51_C := C_}) (Hidden if 51N1P := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51N1P := OFF) 51N1RS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51N1CT :=<br />

(Hidden if 51N1P := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec)<br />

51N1MR :=<br />

(Hidden if 51N1P := OFF)<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51N1P := OFF) 51N1TC :=<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.}, 0.10–3.20 A<br />

{1 A nom.}, 0.13–2.00 mA {2.5 mA nom.}, 5.0–160.0 mA<br />

{50 mA nom.})<br />

51N2P :=<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51N2C :=<br />

(Hidden if 51N2P := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_}, 0.05–1.00 {if 51N2TD :=<br />

51_C := C_}) (Hidden if 51N2P := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51N2P := OFF) 51N2RS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51N2CT :=<br />

(Hidden if 51N2P := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec)<br />

51N2MR :=<br />

(Hidden if 51N2P := OFF)<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51N2P := OFF) 51N2TC :=<br />

Residual Time Overcurrent<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.}, 0.10–3.20 A<br />

{1 A nom.})<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)<br />

(Hidden if 51G1P := OFF)<br />

51G1P :=<br />

51G1C :=<br />

Date Code 20090501 Instruction Manual <strong>SEL</strong>-<strong>751A</strong> Relay