03.09.2015 Views

SEL-751A Settings Sheets - CacheFly

SEL-751A Settings Sheets - CacheFly

SEL-751A Settings Sheets - CacheFly

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SET.4<br />

of 66<br />

<strong>SEL</strong>-<strong>751A</strong> <strong>Settings</strong> <strong>Sheets</strong><br />

Group <strong>Settings</strong> (SET Command)<br />

Date________________<br />

EM RESET DELAY (Y, N) (Hidden if 51BP := OFF) 51BRS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51BCT :=<br />

(Hidden if 51BP := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec) (Hidden if 51BP := OFF) 51BMR :=<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51BP := OFF) 51BTC :=<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.},<br />

51CP :=<br />

0.10–3.20 A {1 A nom.})<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51CC :=<br />

(Hidden if 51CP := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_},<br />

51CTD :=<br />

0.05–1.00 {if 51_C := C_}) (Hidden if 51CP := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51CP := OFF) 51CRS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51CCT :=<br />

(Hidden if 51CP := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec) (Hidden if 51CP := OFF) 51CMR :=<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51CP := OFF) 51CTC :=<br />

Maximum Phase Time Overcurrent<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.},<br />

51P1P :=<br />

0.10–3.20 A {1 A nom.})<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51P1C :=<br />

(Hidden if 51P1P := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_},<br />

51P1TD :=<br />

0.05–1.00 {if 51_C := C_}) (Hidden if 51P1P := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51P1P := OFF) 51P1RS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51P1CT :=<br />

(Hidden if 51P1P := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec)<br />

51P1MR :=<br />

(Hidden if 51P1P := OFF)<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51P1P := OFF) 51P1TC :=<br />

TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.},<br />

51P2P :=<br />

0.10–3.20 A {1 A nom.})<br />

TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51P2C :=<br />

(Hidden if 51P2P := OFF)<br />

TOC TIME DIAL (0.50–15.00 {if 51_C := U_},<br />

51P2TD :=<br />

0.05–1.00 {if 51_C := C_}) (Hidden if 51P2P := OFF)<br />

EM RESET DELAY (Y, N) (Hidden if 51P2P := OFF) 51P2RS :=<br />

CONST TIME ADDER (0.00–1.00 sec)<br />

51P2CT :=<br />

(Hidden if 51P2P := OFF)<br />

MIN RESPONSE TIM (0.00–1.00 sec)<br />

51P2MR :=<br />

(Hidden if 51P2P := OFF)<br />

TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51P2P := OFF) 51P2TC :=<br />

<strong>SEL</strong>-<strong>751A</strong> Relay Instruction Manual Date Code 20090501

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!