Date _______________<br />
<strong>SEL</strong>-<strong>751A</strong> <strong>Settings</strong> <strong>Sheets</strong><br />
Group <strong>Settings</strong> (SET Command)<br />
SET.3<br />
of 66<br />
RES OC TRIP DLY (0.00–5.00 sec) (Hidden if 50G3P := OFF) 50G3D :=<br />
RES OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50G3P := OFF) 50G3TC :=<br />
RES OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50G4P :=<br />
0.10–20.00 A {1 A nom.})<br />
RES OC TRIP DLY (0.00–5.00 sec) (Hidden if 50G4P := OFF) 50G4D :=<br />
RES OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50G4P := OFF) 50G4TC :=<br />
Negative-Sequence Overcurrent<br />
NSEQ OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50Q1P :=<br />
0.10–20.00 A {1 A nom.})<br />
NSEQ OC TRIP DLY (0.1–120.0 sec) (Hidden if 50Q1P := OFF) 50Q1D :=<br />
NSEQ OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50Q1P := OFF) 50Q1TC :=<br />
NSEQ OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50Q2P :=<br />
0.10–20.00 A {1 A nom.})<br />
NSEQ OC TRIP DLY (0.1–120.0 sec) (Hidden if 50Q2P := OFF) 50Q2D :=<br />
NSEQ OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50Q2P := OFF) 50Q2TC :=<br />
NSEQ OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50Q3P :=<br />
0.10–20.00 A {1 A nom.})<br />
NSEQ OC TRIP DLY (0.1–120.0 sec) (Hidden if 50Q3P := OFF) 50Q3D :=<br />
NSEQ OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50Q3P := OFF) 50Q3TC :=<br />
NSEQ OC TRIP LVL (OFF, 0.50–100.00 A {5 A nom.}, 50Q4P :=<br />
0.10–20.00 A {1 A nom.})<br />
NSEQ OC TRIP DLY (0.1–120.0 sec) (Hidden if 50Q4P := OFF) 50Q4D :=<br />
NSEQ OC TRQ CON (<strong>SEL</strong>OGIC) (Hidden if 50Q4P := OFF) 50Q4TC :=<br />
Phase Time Overcurrent<br />
TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.},<br />
51AP :=<br />
0.10–3.20 A {1 A nom.})<br />
TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) 51AC :=<br />
(Hidden if 51AP := OFF)<br />
TOC TIME DIAL (0.50–15.00 {if 51_C := U_}, 0.05–1.00 {if 51ATD :=<br />
51_C := C_}) (Hidden if 51AP := OFF)<br />
EM RESET DELAY (Y, N) (Hidden if 51AP := OFF) 51ARS :=<br />
CONST TIME ADDER (0.00–1.00 sec)<br />
51ACT :=<br />
(Hidden if 51AP := OFF)<br />
MIN RESPONSE TIM (0.00–1.00 sec) (Hidden if 51AP := OFF) 51AMR :=<br />
TOC TRQ CONTROL (<strong>SEL</strong>OGIC) (Hidden if 51AP := OFF) 51ATC :=<br />
TOC TRIP LVL (OFF, 0.50–16.00 A {5 A nom.},<br />
0.10–3.20 A {1 A nom.})<br />
TOC CURVE <strong>SEL</strong> (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)<br />
(Hidden if 51BP := OFF)<br />
TOC TIME DIAL (0.50–15.00 {if 51_C := U_},<br />
0.05–1.00 {if 51_C := C_}) (Hidden if 51BP := OFF)<br />
51BP :=<br />
51BC :=<br />
51BTD :=<br />
Date Code 20090501 Instruction Manual <strong>SEL</strong>-<strong>751A</strong> Relay