<strong>Installation</strong><br />

Remote Mounted Thermostat<br />

Option<br />

Mount the thermostat in the largest<br />

space occupied by the most people for<br />

the best average temperature sensing.<br />

The thermostat should be mounted about<br />

5 feet from the floor in contact with freely<br />

circulating air, but not with major drafts.<br />

Avoid the following areas:<br />

Behind doors or in corners where ther is<br />

no free circulation.<br />

Locations where the sun’s rays or<br />

infrared radiation from appliances or<br />

fireplaces may affect thermostat<br />

operation.<br />

Surfaces subject to vibration.<br />

On walls that contact outside air.<br />

Adjacent to or in line with conditioned air<br />

discharge grilles or doorways.<br />

Remote Mounted Thermostat Wiring<br />

After the thermostat is mounted, wire the<br />

thermostat back to the unit control panel<br />

according to the correct diagram shown<br />

on inside of panel door.<br />

The total resistance of the thermostat <strong>and</strong><br />

the control wiring to each terminal must<br />

Pre-Startup<br />

Requirements<br />

not exceed 1 ohm. Table I-PR-6 provides<br />

recommended wire sizes for length of<br />

run.<br />

Wiring the Remote Air-cooled CCRC <strong>and</strong><br />

SCRG<br />

The SCRG/SIRG air-cooled condenser<br />

should be wired to the control panel of<br />

the SCRG/SIRG unit to ensure proper<br />

system operation. Reference unit wiring<br />

diagrams for correct terminal locations.<br />

Table I-PR-3 provides recommended<br />

wires sizes for length of run.<br />

Table I-PR-6. Control Wire Size <strong>and</strong> Maximum<br />

Length<br />

Wire Gauge Max. Wire Length<br />

22 30 ft.<br />

20 50 ft.<br />

18 75 ft.<br />

16 125 ft.<br />

14 200 ft.<br />

50 SCXG-SVX01B-EN