<strong>Installation</strong><br />
Remote Mounted Thermostat<br />
Option<br />
Mount the thermostat in the largest<br />
space occupied by the most people for<br />
the best average temperature sensing.<br />
The thermostat should be mounted about<br />
5 feet from the floor in contact with freely<br />
circulating air, but not with major drafts.<br />
Avoid the following areas:<br />
Behind doors or in corners where ther is<br />
no free circulation.<br />
Locations where the sun’s rays or<br />
infrared radiation from appliances or<br />
fireplaces may affect thermostat<br />
operation.<br />
Surfaces subject to vibration.<br />
On walls that contact outside air.<br />
Adjacent to or in line with conditioned air<br />
discharge grilles or doorways.<br />
Remote Mounted Thermostat Wiring<br />
After the thermostat is mounted, wire the<br />
thermostat back to the unit control panel<br />
according to the correct diagram shown<br />
on inside of panel door.<br />
The total resistance of the thermostat <strong>and</strong><br />
the control wiring to each terminal must<br />
Pre-Startup<br />
Requirements<br />
not exceed 1 ohm. Table I-PR-6 provides<br />
recommended wire sizes for length of<br />
run.<br />
Wiring the Remote Air-cooled CCRC <strong>and</strong><br />
SCRG<br />
The SCRG/SIRG air-cooled condenser<br />
should be wired to the control panel of<br />
the SCRG/SIRG unit to ensure proper<br />
system operation. Reference unit wiring<br />
diagrams for correct terminal locations.<br />
Table I-PR-3 provides recommended<br />
wires sizes for length of run.<br />
Table I-PR-6. Control Wire Size <strong>and</strong> Maximum<br />
Length<br />
Wire Gauge Max. Wire Length<br />
22 30 ft.<br />
20 50 ft.<br />
18 75 ft.<br />
16 125 ft.<br />
14 200 ft.<br />
50 SCXG-SVX01B-EN