RSM 1CO/2CO – Relay <strong>interface</strong><br />
1 or 2 changeover<br />
• Interface from 4 to 16 electromechanical relays<br />
• 1 or 2 changeover<br />
• Positive or negative switching or ac/dc<br />
• With optional test button with latching function<br />
(RCI relays)<br />
• Empty boards available (BASE)<br />
• Flat-connector avaliable to make easy the connection to <strong>PLC</strong>’S<br />
• Compatible with solid-state relays<br />
• Screw <strong>and</strong> “PUSH IN” for 1 changeover<br />
• Screw <strong>and</strong> tension clamp for 2 changeover<br />
RSM multiple relay modules – Interfaces with 12,5mm relays (RCL)<br />
Isolated Interfaces <strong>and</strong> solutions for general<br />
applications<br />
General technical data<br />
General features 1 changeover 2 changeover<br />
Relay RCL (st<strong>and</strong>ard) / RCI (test button) RCL (st<strong>and</strong>ard) / RCI (test button)<br />
LED status display per channel Green Green<br />
LED status of the supply voltage Yellow Yellow<br />
Nominal output data<br />
Contact material AgNi 90/10 AgNi 90/10<br />
Operative voltage 250 V AC 250 V AC<br />
Max. AC continuous current 6 A 5 A<br />
Minimum contact current 100 mA 100 mA<br />
Minimum contact voltage 5 V DC 5 V DC<br />
Mechanical service life (dc coil) 30 x 10 6 / 10 x 10 6 (RCI) switchings 30 x 10 6 / 10 x 10 6 (RCI) switchings<br />
Mechanical service life (ac coil) 10 x 10 6 / 5 x 10 6 (RCI) switching cycles 5 x 10 6 switching cycles<br />
Operating temperature -25...+50 °C -25...+50 °C<br />
Storage temperature -40...+60 °C -40...+60 °C<br />
Insulation coordination (EN 50178)<br />
Rated input insulation voltage < 50 V AC < 50 V AC<br />
Rated output insulation voltage 250 V AC 250 V AC<br />
Overvoltage category input/output III III<br />
Overvoltage category input/output II III<br />
Pollution severity level 2 2<br />
Impulse voltage test (1.2/50µs) 6 kV 6 kV<br />
Insulation test voltage 1.2 kV AC 1.2 kV AC<br />
Clearance input/output ≥ 5.5 mm ≥ 5.5 mm<br />
Dimensions Screw connection PUSH IN Screw connection Tension clamp<br />
Clamping range, min. [Field]/ Clamping range, max. [Field] 0.13 mm 2 / 6 mm 2 0.12 mm 2 / 2.5 mm 2 0.13 mm 2 / 6 mm 2 0.13 mm 2 / 2.5 mm 2<br />
Clamping range, min. [supply]/Clamping range, max. [supply] 0.13 mm 2 / 6 mm 2 0.12 mm 2 / 2.5 mm 2 0.13 mm 2 / 6 mm 2 0.13 mm 2 / 2.5 mm 2<br />
Mounting rail TS 32 / TS 35 TS 32 / TS 35 TS 32 / TS 35 TS 32 / TS 35<br />
Width / height mm 87 x 66 87 x 66 109 x 71 109 x 66<br />
Width / height (RCI) mm 87 x 77 87 x 77 109 x 75 109 x 75<br />
Width / height (BASE) mm 87 x 53 87 x 51<br />
Note<br />
Electromechanical relays:<br />
12 V DC: Spare relay RCL314012 8693240000;<br />
24 V DC: Spare relay RCL314024 8693260000;<br />
24 V AC/DC: Spare relay relay RCL314024 8693260000;<br />
48 V DC: Spare relay RCL31404 8693380000;<br />
115 V AC/DC: Spare relay RT314110 4058500000;<br />
230 V AC: Spare relay RCL314730 8693320000.<br />
Solid-state relays:<br />
SSR 24 V DC/0-24 V DC 3.5 A 1132310000;<br />
SSR 24 V DC/max. 240 V AC 1 A 113229000.<br />
RCI relay:<br />
Spare relay RCI374024 8869960000<br />
Electromechanical relays:<br />
12 V DC: Spare relay RCL424012 4058560000;<br />
24 V DC: Spare relay RCL424024 4058570000;<br />
24 V AC/DC: Spare relay RCL424024 4058570000;<br />
48 V DC: Spare relay RCL424048 4058750000;<br />
115 V AC/DC: Spare relay RCL424110 4058590000;<br />
230 V AC: Spare relay RCL424730 4058630000;<br />
RCI relay:<br />
Spare relay RCI484024 8870030000<br />
E<br />
2021570000<br />
E.5