Weidmueller PLC-interface units, front adapters and prefabricated cables.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
RSM – Isolated <strong>interface</strong>s for digital output signals<br />
RSM – Isolated <strong>interface</strong>s<br />
for 16 digital output signals<br />
Digital output relay <strong>interface</strong> for transmitting electrical<br />
signals between the <strong>PLC</strong> <strong>and</strong> the field via pre-wired <strong>cables</strong><br />
of Weidmüller’s universal system.<br />
• Input/output reinforced insulation (basic between<br />
contacts)<br />
• Positive switching<br />
RSM-16 FUS 1CO<br />
RCL relays, 1 CO contact with fuse relay contact<br />
Universal solutions for <strong>PLC</strong> input/<br />
output cards<br />
A<br />
Technical data<br />
Connection data <strong>and</strong> functionality<br />
Connection on control side<br />
Number of poles (control side)<br />
Relay type<br />
LED status display per relay<br />
LED status of the supply voltage<br />
Fuse per relay<br />
Power supply fuse<br />
Nominal input data<br />
Input voltage<br />
Input current<br />
Operating voltage (supply)<br />
Operating current (supply)<br />
Nominal output data<br />
Contact material<br />
Operating voltage<br />
Max. AC continuous current<br />
Minimum contact current<br />
Minimum contact voltage<br />
Mechanical service life<br />
General data<br />
Ambient temperature (operational)<br />
Storage temperature<br />
Approvals<br />
Insulation coordination (EN 50178)<br />
Rated input insulation voltage<br />
Rated output insulation voltage<br />
Overvoltage category input/output<br />
Overvoltage category output/output<br />
Pollution severity level<br />
Pulse voltage test (1,2/50μs)<br />
Insulation test voltage<br />
Clearance input/output<br />
Dimensions<br />
Clamping range, min./max. (field)<br />
Clamping range, min./max. (supply)<br />
Mounting rail<br />
Length x width<br />
Note<br />
Connector according IEC60603-13/DIN41651<br />
20-pole plug<br />
RCL<br />
green<br />
yellow<br />
5 A<br />
3.15 A<br />
24 V DC ± 10%<br />
20 mA<br />
24 V DC ± 10%<br />
2 A<br />
AgNi 90/10<br />
250 V AC<br />
5 A<br />
0.01 A<br />
10 V<br />
3 x 10 7 switching cycles<br />
-25...40°C<br />
-40...60 °C<br />
CE; EAC<br />
< 50 V AC<br />
< 250 V AC<br />
III<br />
II<br />
2<br />
6 kV<br />
1.2 kVAC<br />
≥ 5.5 mm<br />
Screw connection<br />
Tension-clamp connection<br />
0.13 mm² / 6 mm² 0.15 mm² / 1.5 mm²<br />
0.13 mm² / 6 mm² 0.15 mm² / 1.5 mm²<br />
TS 35, TS 32 TS 35, TS 32<br />
261 mm / 109 mm 261 mm / 109 mm<br />
Ordering data<br />
Note<br />
Accessories<br />
Note<br />
Screw connection without switch<br />
Screw connection with switch<br />
Tension-clamp connection without switch<br />
Tension-clamp connection with switch<br />
Type Height Order No.<br />
RSM-16 FUS 1CO S 75 mm 9445120000<br />
RSM-16 FUS 1CO Z 75 mm 9447120000<br />
Relay 8693260000 RCL314024 24 V DC 1CO<br />
2021570000<br />
A.81