06.11.2019 Views

Weidmueller PLC-interface units, front adapters and prefabricated cables.

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TERMSERIES <strong>adapters</strong><br />

• Suitable for input <strong>and</strong> output logic<br />

• Version for 6.4mm TERMSERIES base<br />

• Supply connections (PUSH IN) in double execution for<br />

supply voltage bridging<br />

• User-friendly <strong>and</strong> unmistakable marking<br />

• 20-pin connecting plug according to DIN EN 60603-13<br />

TIAL F20<br />

Potential change-over switch<br />

TERMSERIES <strong>adapters</strong><br />

Isolated Interfaces <strong>and</strong> solutions for general<br />

applications<br />

<br />

<br />

The potential change-over switch is located between contact rows of<br />

the TERMSERIES adaptor. It is used to switch the potential of the lower<br />

contact row to “+” or “-” potential of the supply voltage.<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Installation input<br />

Technical data<br />

Supply<br />

Supply voltage<br />

Status display<br />

Signals<br />

Rated voltage<br />

Voltage, max.<br />

Rated current (per signal path)<br />

Current (per signal path), max.<br />

Total current of all signals, max.<br />

Number of signal paths<br />

Connection data (supply)<br />

Wire connection method<br />

Clamping range, rated connection, min.<br />

Clamping range, rated connection, max.<br />

Number of terminals<br />

Connection data (signal)<br />

Plug type<br />

General data<br />

Ambient temperature (operational)<br />

Storage temperature<br />

Humidity<br />

UL 94 flammability rating<br />

Approvals<br />

Insulation coordination<br />

Pollution degree<br />

Overvoltage category<br />

Impulse withst<strong>and</strong> voltage<br />

Rated voltage<br />

Protection degree<br />

24 V DC ± 20 %<br />

Green LED<br />

24 V DC<br />

30 V DC<br />

60 mA<br />

1 A<br />

1 A<br />

16<br />

PUSH IN<br />

0.13 mm²<br />

1.5 mm²<br />

4 (+,+,−,−)<br />

20-pole plug according to DIN EN 60603-13, long locking lever<br />

-40 °C...60 °C<br />

-40 °C...85 °C<br />

5...95% (indoor), T u<br />

= 40°C, no condensation<br />

V-0<br />

CE; cULus; GL<br />

2<br />

III<br />

1.5 kV<br />

32 V<br />

IP 20 in installed condition<br />

A1 +<br />

24V<br />

TOS<br />

TRS<br />

14 11 12 A1 A2<br />

24V<br />

14<br />

A2 -<br />

A1 +<br />

24V<br />

TOS<br />

TRS<br />

14 11 A1 A2<br />

14 11 12 A1 A2<br />

24V<br />

Figure 1a<br />

Figure 1b<br />

NO<br />

14<br />

COM<br />

1122770000<br />

TRS 24VDC 1CO<br />

Figure 1a: Positive-switching logic: Potential change-over<br />

switch to “-”, installation on 24 V DC input (A1/A2).<br />

Figure 1b: Negative-switching logic: Potential change-over<br />

switch to “+”, installation on 24 V UC input (A1/A2).<br />

Installation output<br />

14 11 A1 A2<br />

NO<br />

COM<br />

11<br />

NC<br />

12<br />

E<br />

12<br />

NC<br />

A2 -<br />

11<br />

1122770000<br />

TRS 24VDC 1CO<br />

Figure 2a<br />

Dimensions<br />

Depth x width x height<br />

Note<br />

mm<br />

62 / 102 / 43<br />

Figure 2b<br />

Figure 2a: Positive-switching logic: Potential change-over<br />

switch to “+”, installation on output (11/14).<br />

Figure 2b: Negative-switching logic: Potential change-over<br />

switch to “-”, installation on output (11/14).<br />

Ordering data<br />

Type Qty. Order No.<br />

TIAL F20 1 1463550000<br />

Note<br />

Suitable for 6.4mm wide TERMSERIES base<br />

Accessories<br />

Note<br />

2021570000<br />

E.53