Isolated Interfaces <strong>and</strong> solutions for general<br />

applications<br />

TERMSERIES <strong>adapters</strong><br />

TERMSERIES <strong>adapters</strong><br />

• Suitable for input <strong>and</strong> output logic<br />

• Version for 12.8mm TERMSERIES base<br />

• Supply connections (PUSH IN) in double execution for<br />

supply voltage bridging<br />

• User-friendly <strong>and</strong> unmistakable marking<br />

• 10-pin connector according to DIN EN 60603-13<br />

TIAL F10<br />

Potential change-over switch<br />

<br />

<br />

The potential change-over switch is located between contact rows of<br />

the TERMSERIES adaptor. It is used to switch the potential of the lower<br />

contact row to “+” or “-” potential of the supply voltage.<br />

<br />

<br />

<br />

<br />

<br />

<br />

Installation input<br />

E<br />

Technical data<br />

Supply<br />

Supply voltage<br />

Status display<br />

Signals<br />

Rated voltage<br />

Voltage, max.<br />

Rated current (per signal path)<br />

Current (per signal path), max.<br />

Total current of all signals, max.<br />

Number of signal paths<br />

Connection data (supply)<br />

Wire connection method<br />

Clamping range, rated connection, min.<br />

Clamping range, rated connection, max.<br />

Number of terminals<br />

Connection data (signal)<br />

Plug type<br />

General data<br />

Ambient temperature (operational)<br />

Storage temperature<br />

Humidity<br />

UL 94 flammability rating<br />

Approvals<br />

Insulation coordination<br />

Pollution degree<br />

Overvoltage category<br />

Impulse withst<strong>and</strong> voltage<br />

Rated voltage<br />

Protection degree<br />

24 V DC ± 20 %<br />

Green LED<br />

24 V DC<br />

30 V DC<br />

125 mA<br />

1 A<br />

1 A<br />

8<br />

PUSH IN<br />

0.13 mm²<br />

1.5 mm²<br />

4 (+,+,−,−)<br />

10-pole plug according to DIN EN 60603-13, long locking lever<br />

-40 °C...60 °C<br />

-40 °C...85 °C<br />

5...95% (indoor), T u<br />

= 40°C, no condensation<br />

V-0<br />

CE; cULus; GL<br />

2<br />

III<br />

1.5 kV<br />

32 V<br />

IP 20 in installed condition<br />

A1 +<br />

24V<br />

TOS<br />

TRS<br />

14 11 12 A1 A2<br />

24V<br />

14<br />

A2 -<br />

A1 +<br />

24V<br />

TOS<br />

TRS<br />

14 11 A1 A2<br />

14 11 12 A1 A2<br />

24V<br />

Figure 1a<br />

Figure 1b<br />

NO<br />

14<br />

COM<br />

1122770000<br />

TRS 24VDC 1CO<br />

Figure 1a: Positive-switching logic: Potential change-over<br />

switch to “-”, installation on 24 V DC input (A1/A2).<br />

Figure 1b: Negative-switching logic: Potential change-over<br />

switch to “+”, installation on 24 V UC input (A1/A2).<br />

Installation output<br />

14 11 A1 A2<br />

NO<br />

11<br />

NC<br />

A2 -<br />

11<br />

12<br />

12<br />

NC<br />

COM<br />

1122770000<br />

TRS 24VDC 1CO<br />

Figure 2a<br />

Dimensions<br />

Depth x width x height<br />

Note<br />

mm<br />

62 / 102 / 43<br />

Figure 2b<br />

Figure 2a: Positive-switching logic: Potential change-over<br />

switch to “+”, installation on output (11/14).<br />

Figure 2b: Negative-switching logic: Potential change-over<br />

switch to “-”, installation on output (11/14).<br />

Ordering data<br />

Type Qty. Order No.<br />

TIAL F10 1 1463540000<br />

Note<br />

Suitable for 12.8mm wide TERMSERIES base<br />

Accessories<br />

Note<br />

E.52 2021570000