High Intensity Discharge<br />

Ballast Data – Mercury Vapor<br />

Mercury vapor lamps from 175 watts through<br />

1000 watts will operate satisfactorily on equivalent-wattage<br />

probe start metal halide ballasts.<br />

For electrical characteristics of these wattages,<br />

see metal halide ballast information.<br />

Open Minimum<br />

ANSI Ballast Power Wiring Regulation Starting Primary Dropout Starting Operating Circuit Input<br />

Wattage Code Type Factor Diagram LineV=LampW Ambient Voltage Voltage Current Current Current Wattage<br />

50 H46 HX NPF M1 less cap +/-5%=+/-12% -30C/-20F 120 80 2.10 1.50 0.25 74<br />

H46 CWA HPF M2 +/-10%=+/-10% -30C/-20F 120/277 60/138 0.60/0.25 0.70/0.30 0.25/0.11 74<br />

75 H43 HX NPF M1 less cap +/-5%=+/-12% -30C/-20F 120 102 2.60 1.60 0.30 96<br />

H43 CWA HPF M2 +/-10%=+/-10% -30C/-20F 120/277 64/145 0.80/0.35 0.90/0.40 0.50/0.22 93<br />

100 H38 or H44 HX NPF M1 less cap +/-5%=+/-12% -30C/-20F 120 90 3.60 2.10 0.50 125<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 120 65 0.68 1.05 0.52 123<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 208 110 0.44 0.60 0.36 125<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 240 130 0.39 0.52 0.31 125<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 277 150 0.34 0.45 0.28 125<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 347 180 0.38 0.38 0.22 125<br />

H38 or H44 CWA HPF M2 +/-10%=+/-10% -30C/-20F 480 230 0.26 0.26 0.16 120<br />

600 Lamps and Ballasts / PSG8<br />

www.AcuityBrandsLighting.com<br />

HAZARD WARNING – USE OF MERCURY VAPOR LAMPS<br />

These lamps can cause serious skin burns and eye inflammation<br />

from ultraviolet radiation if the outer envelope<br />

of the lamp is broken or punctured and the arc-tube<br />

continues to operate. Do not use where people will<br />

remain for more than a few minutes unless adequate<br />

shielding or other safety precautions are used. Certain<br />

types of lamps that will automatically extinguish when<br />

the outer envelope is broken are commercially available.