38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Main Plant Controllers<br />
CXT<br />
PID Pulse 24V<br />
Controller<br />
CZT<br />
PID 0-10Vdc<br />
Controller<br />
Keyboard<br />
FLS<br />
C/O Step Control<br />
Function Module<br />
KMC<br />
Multiple<br />
Application PID<br />
Controller<br />
The CXT Controller is primarily designed to control systems<br />
with short time constants and fast response times. This<br />
would typically be the control of heat exchangers, non<br />
storage calorifiers or ventilation plant where the sensor is<br />
placed directly in the controlled medium. The CXT operates<br />
24Vac actuators on two or three port valves. It is capable of<br />
operating single or two stage systems.<br />
FEATURES<br />
• Easy to install and commission<br />
• Shipped with typical default values for the<br />
parameters, decreasing commissioning time<br />
• Quick set mode allows basic settings to be easily<br />
checked and set<br />
• Simple override switch<br />
• Operates single or two stage systems<br />
• Night Set Back (NSB) and set-up inputs<br />
• Supports new or old generation <strong>Satchwell</strong> sensors<br />
• Remote setting input for room set value (RPW)<br />
• Cost effective upgrade of all obsolete Climatronic<br />
controllers<br />
The CZT Controller is designed for use in systems such as<br />
room or return water control. the CZT can be used for single<br />
or two stage control. the CZT is suitable for use with 0 to<br />
10Vdc actuators and/or step controllers.<br />
FEATURES<br />
• Easy to install and commission<br />
• Shipped with typical default values for the<br />
parameters, decreasing commissioning time<br />
• Quick set mode allows basic settings to be easily<br />
checked and set<br />
• Simple override switch<br />
• Operates single or two stage systems<br />
• Standard 0...10Vdc output<br />
• Night Set Back (NSB) and set-up inputs<br />
• Existing CZT sensors can be used<br />
• Remote setting input for room set value (RPW)<br />
• Cost effective upgrade of all obsolete Climatronic<br />
controllers<br />
The FLS is a Step Control Function Module which is<br />
designed to be used in conjunction with<br />
0 to 10Vdc output Controllers thus providing a stepped<br />
on/off output from one or more stages.<br />
FEATURES<br />
• Six steps available<br />
• Indication LEDs show status of each relay step<br />
• Provides step control of electric heaters and alike<br />
• Panel mounting optional<br />
The KMC Controller can be used to control humidity or<br />
temperature in ventilation and air conditioning systems. The<br />
KMC uses <strong>Satchwell</strong> sensors to monitor humidity or<br />
temperature and control the plant.<br />
The KMC is designed to carry out the general control<br />
functions of the <strong>Satchwell</strong> KZT, KZH and KET controllers with<br />
the added benefit of a digital display.<br />
The KMC control stage outputs are all 0...10Vdc, except the<br />
single stage humidity application that has an optional 24Vac<br />
pulsed output.<br />
The controller can be configured to run in one of the<br />
applications by simply selecting that application number.<br />
1. Single Stage Humidity Controller<br />
2. Two Stage Humidity Controller<br />
3. Single Stage Temperature Controller<br />
4. Two Stage Temperature Controller<br />
5. Three Stage Temperature Controller<br />
FEATURES<br />
• Direct digital control<br />
• Programmed via the keyboard and display<br />
• Digital display provides comprehensive indications of<br />
all current parameter values, settings and<br />
measurements<br />
PRODUCT SELECTION<br />
18<br />
Control Output<br />
CXT 56<strong>05</strong> Single or two stage 24V actuator control<br />
Data Sheet 2.101<br />
INSTALLATION DETAILS<br />
Power supply - 230Vac (+10%, –6%) 50/60Hz<br />
Power failure reserve - Settings stored in memory, 1 year battery for clock<br />
Protection class - IP 30<br />
Switched inputs - Night Set Back (NSB): Voltage free, make/break contacts.<br />
Normally closed.<br />
Set Up: Voltage free, make/break contacts. Normally closed.<br />
Outputs - Valve Actuator Output Triacs: 2 x 24Vac triacs, 1A (0V switched and software<br />
interlocked).<br />
Output Supply: 2 x 24Vac terminals used to power the actuator up to a total of<br />
10VA maximum.<br />
Sensor inputs - ‘T’ type sensors<br />
Sensor types - DDT 0001, DWT 0001, DST 0001, RPW 4425 (see table on previous page)<br />
Control Output<br />
CZT 53<strong>05</strong> Single or two stage 0...10Vdc for heating and cooling<br />
Data Sheet 2.1<strong>05</strong><br />
<strong>Satchwell</strong> Controllers<br />
INSTALLATION DETAILS<br />
Power supply - 230Vac (+10%, –6%) 50/60Hz<br />
Power failure reserve - Settings stored in memory, 1 year battery for clock<br />
Protection class - IP 30<br />
Switched inputs - Night Set Back (NSB): Voltage free, make/break contacts.<br />
Normally closed.<br />
Set Up: Voltage free, make/break contacts. Normally closed.<br />
Outputs - Control outputs: 2 x 0...10Vdc outputs for heating and cooling.<br />
Output Supply: 2 x 24Vac terminals used to power the actuator(s) up to a total of<br />
10VA maximum.<br />
Sensor inputs - ‘T’ type sensors.<br />
Sensor types - DRT 3651, 3453, 3451, DDT 0001, DWT 0001, DST 0001, RPW 4425<br />
(see table on previous page)<br />
Control Input Relays Voltage Free ContactsPower Supply<br />
FLS 1502 0...10Vdc 6 230Vac, 2A (IA inductive) 24Vac<br />
Data Sheet 2.195<br />
Associated input devices - IAC, MMC, CZT, KMC<br />
INSTALLATION DETAILS<br />
Running time though 0...10V stroke - 180 seconds (adjustable 60 to 720 seconds)<br />
Protection class - IP 40 when flush mounted<br />
ACCESSORY 866-1-4<strong>05</strong> Panel Mounting Kit<br />
Control Range Output Power Supply<br />
KMC 3201 PID –40…+150°C 0...10Vdc 24Vac<br />
3-stage temp. 0…100% rh for heating<br />
2-stage humidity or cooling<br />
Data Sheet 2.120<br />
FEATURES (cont)<br />
• Low voltage (24Vac)<br />
• Proportional + Integral + Derivative control action for stable control<br />
without offset<br />
• Default programme of typical settings for each parameter operates on<br />
initial start-up<br />
• Security code prevents unauthorised access to setting parameters<br />
• Five applications to deal with most humidity and temperature control schemes,<br />
see the previous section for details of each scheme<br />
• The KMC can be used in place of the <strong>Satchwell</strong> KZT, KZH and KET controllers<br />
• Real Time Clock (RTC) on the two humidity applications<br />
INSTALLATION DETAILS<br />
Power failure reserve - Settings stored in memory, 5 year battery for clock<br />
Inputs - Sensors: DRT, DDT, DOT, DRH, DDH<br />
Outputs - Actuators: ALi, ALE, ALES, AVUE<br />
24Vac switched outputs: 2 x digital outputs, ALX, ALXS, ARX<br />
Protection class - IP 40 when flush mounted