Duct Temperature Thermostats, Pressure and Air Flow Switches<br />

TDR, TDC<br />

Air Temperature<br />

Thermostats<br />

SPA<br />

Universal<br />

Differential and<br />

Universal Pressure<br />

Switches<br />

SFA<br />

Air Flow Switch<br />

SPA<br />

Air Differential<br />

Pressure Switch<br />

Pipe Temperature Thermostats and Flow Switches<br />

SFW<br />

Water Flow Switch<br />

TWK<br />

Water Immersion<br />

Thermostat<br />

TWL, TWM<br />

Water Immersion<br />

Thermostats<br />

(manual reset)<br />

These thermostats are for duct applications and incorporate<br />

a single pole double throw contact switch.<br />

FEATURES<br />

• Simple installation and commissioning<br />

• Cable gland supplied<br />

The SPA 1501…1504 Differential Pressure Switches can be<br />

used to signal when the pressure difference is too high due<br />

to a blocked filter, too low due to flow failure, or for level<br />

control in a pressurised vessel. Suitable for use on a vacuum.<br />

The SPA 15<strong>05</strong> &1506 Pressure Switches can be wired into<br />

control circuits or contactors to provide a high or low<br />

pressure cut-out. Alternatively, they can be wired directly to<br />

a bell or light to provide a high or low pressure alarm. Not<br />

suitable for use on a vacuum.<br />

This switch is designed to control air flow using a paddle to<br />

switch on and off the power supply. The paddle can be<br />

trimmed if the air flow is above 5 metres per second.<br />

The SPA Differential Pressure Switch is used to monitor<br />

non-inflammable and non-aggressive gases. Typical<br />

applications are filter dirty and fan run/stop detection.<br />

ACCESSORY DDP 3601 Fitting Kit (containing 2 metres of<br />

PVC tubing and 2 duct mounting pitot tubes)<br />

The SFW Flow Switch is designed to control water flow, in<br />

pipe diameters from 1” to 6”, using a paddle to switch on<br />

and off the power supply. The paddle can be trimmed to<br />

suit the flow required. It is designed to be mounted in a<br />

short necked welded socket or a tee with a short branch.<br />

The TWK Thermostat is for water applications and<br />

incorporate a single pole double throw contact switch.<br />

FEATURES<br />

• Simple installation and commissioning<br />

• Cable gland supplied<br />

These thermostats are typically used in water high<br />

limit/control applications such as HWS cylinders or boilers.<br />

The TWL is a manual reset, high limit thermostat with a<br />

Single Pole Double Throw (SPDT) action. The TWM is a<br />

combined control thermostat and manual reset, high limit<br />

thermostat allowing independent setting of both the control<br />

point and high limit temperature.<br />

FEATURES<br />

• Simple installation and commissioning<br />

• Cable gland supplied<br />

• Manual reset<br />

• Concealed setting for reset temperature<br />

PRODUCT SELECTION <strong>Satchwell</strong> Switches & Thermostats<br />

26<br />

Max fluid temp. Contact rating<br />

SFW 1251 85°C 24...230Vac, 15A<br />

single pole, double throw<br />

Data Sheet 21.670<br />

Head protection class - IP 65<br />

Sensing range Adjustment Pocket Contact rating<br />

TWK 2301 0...90°C Exposed 1 /2” NPT 230Vac, 16A<br />

(100mm x 8mm Ø) SPDT<br />

Data Sheet 21.001<br />

Sensing range Adjustment Stem type Contact rating<br />

TDR 2201 0...60°C Exposed Rigid stem 230Vac, 16A<br />

(190mm x 8mm Ø) SPDT<br />

TDC 2202 0...60°C Exposed Capillary stem<br />

(1 metre)<br />

Data Sheet 21.001<br />

Protection class - IP 40<br />

Max head temperature - 80°C<br />

Type Spec. no. Sensing range Reset differential* Contact rating<br />

Universal SPA 1501 150 - 1000 mbar 50 - 100 1A @ 250v<br />

Differential<br />

Pressure<br />

SPA 1502 6 - 20 mbar 3 - 8 1A @ 250v<br />

SPA 1503 15 - 60 mbar 5 - 16 1A @ 250v<br />

SPA 1504 40 - 200 mbar 20 - 60 1A @ 250v<br />

Universal SPA 15<strong>05</strong> 120 - 2200 mbar 110 - 450 6A @ 250v<br />

Pressure<br />

SPA 1506 1000 - 6000 mbar 200 - 1500 6A @ 250v<br />

Protection class - SPA 1501-1504 IP 65, SPA 15<strong>05</strong>/1506 IP 54. *Adjustable between (mbar)<br />

Max line pressure - SPA 1501 - 20 bar, SPA 1502-1504 - 10 bar, SPA 15<strong>05</strong>/1506 - 6 bar<br />

Protection class - IP 40<br />

Max head temperature - 80°C<br />

Sensing range Adjustment Pocket Contact rating<br />

TWL 2302 65...85°C Exposed 1 /2” NPT 230Vac, 16A<br />

(100mm x 8mm Ø) SPDT<br />

TWM 2401 0...90°C (control) Exposed 1 /2” NPT<br />

70...90°C (limit) Concealed (100mm x 16mm Ø)<br />

Data Sheet 21.002<br />

Protection class - IP 40<br />

Max head temperature - 80°C<br />

Flow setting Contact rating<br />

SFA 1451 1 m/s, 2.5 m/s (paddle untrimmed) 24...230Vac, 15A<br />

single pole, double throw<br />

Data Sheet 21.670<br />

Head protection class - IP 65<br />

Adjustable range Max. operating Repeatability Contact<br />

for trip pressure pressure rating<br />

SPA 1401 0.2...3.0 mbar 50 mbar 0.025 mbar 230Vac, 1A<br />

SPDT<br />

SPA 1402 1.0...10.0 mbar 50 mbar 0.<strong>05</strong> mbar<br />

Data Sheet 21.601<br />

Protection class - IP 54<br />

Pressure connection - 2 plastic tubes with inside diameter of 6mm