38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
38059-Satchwell Inter. Guide 05
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Satchwell</strong> Switches & Thermostats<br />
Pipe Temperature Thermostat<br />
TSM<br />
Strap-on Pipe<br />
Thermostat<br />
Transducer<br />
EPT<br />
Electro Pneumatic<br />
Transducer<br />
The TSM Thermostat is typically used in water control<br />
applications where it is not possible to insert a pocket into<br />
the pipe. The thermostat is attached to the pipe by a spring<br />
strap (supplied).<br />
FEATURES<br />
• Simple installation and commissioning<br />
• Cable gland supplied<br />
Outside and Pipe Frost Thermostats<br />
TCL<br />
Air Temperature<br />
Thermostats<br />
The range of TCL Freeze Thermostats covers both outside,<br />
heater battery and water pipe freeze protection.<br />
The TCL 1601 wall mounting freeze thermostat is suitable for<br />
outside mounting.<br />
The TCL 1602 and TCL 1603 have a capillary that will sense<br />
the lowest temperature on the face of the battery or the<br />
surface of a pipe.<br />
This transducer is used as an interface between an electronic<br />
controller and a pneumatically operated control valve or<br />
damper. It is set to receive a 0...10Vdc input and converts it<br />
to a proportional 0...20 PSI output signal. The input may be<br />
configured, if required, for 0...5Vdc or 4...20mA by using the<br />
jumpers on the PCB.<br />
FEATURES<br />
• Smooth stable linear performance<br />
• Choice of input signals to meet most control<br />
applications. 0...10Vdc, 0...5Vdc or 4...20mA selected<br />
from onboard jumpers<br />
• LED indication of supply status and<br />
increasing/decreasing pressure signal<br />
• Indication gauge for actual air pressure output<br />
• Manual override of output pressure signal<br />
PRODUCT SELECTION<br />
27<br />
Input signal Output signal Max supply Input power<br />
pressure<br />
EPT 7401 0...10Vdc 0...20 psi 45 psi 24Vac/dc nominal<br />
0...5vdc or 3...15 psi<br />
4...20mA<br />
Data Sheet 25.021<br />
Sensing range Adjustment Contact rating<br />
TSM 2501<br />
Data Sheet 21.003<br />
0...90°C Exposed 230Vac, 16A<br />
SPDT<br />
Ambient temperature limits - Maximum sensing plate temperature 100°C<br />
Maximum pipe diameter - 150mm<br />
Protection class - IP 40<br />
Sensing range Type Stem type Contact rating<br />
TCL 1601 –15...+10°C Outside – 230Vac SPDT<br />
(auto reset) heating 10A, cooling 3A<br />
TCL 1602 –18...+13°C Coil and pipe Capillary stem 230Vac, 6A<br />
(manual reset) (6m) SPDT<br />
TCL 1603 –18...+13°C Coil and pipe Capillary stem<br />
(auto reset) (6m)<br />
Data Sheet 21.004<br />
INSTALLATION DETAILS<br />
Protection class - TCL 1601: IP 65, TCL 1602/3: IP 43<br />
INSTALLATION DETAILS<br />
Indication - Output air pressure gauge (indication only)<br />
Power on LED<br />
Pressure increasing LED<br />
Pressure decreasing LED